Table – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 217
No.
Parameter Name
Setting
Range
Default
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to 9F
81 (4)
<1>
: HAND Mode 2
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to 9F
F (6)
<1>
: Through Mode
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Table 4.20 Multi-Function Digital Input Terminal Settings
Setting
Function
Page
0
3-Wire sequence
–
2
External Reference 1/2 Selection
–
3
Multi-Step Speed Reference 1
–
4
Multi-Step Speed Reference 2
–
5
Multi-Step Speed Reference 3
–
6
Jog reference selection
–
7
Accel/decel time selection 1
–
8
Baseblock command (N.O.)
–
9
Baseblock command (N.C.)
–
A
Accel/decel ramp hold
–
B
Drive overheat alarm (oH2)
–
C
Analog terminal input selection
–
F
Through mode
–
10
Up command
–
11
Down command
–
12
Forward Jog
–
13
Reverse Jog
–
14
Fault reset
–
15
Fast Stop (N.O.)
–
17
Fast Stop (N.C.)
–
18
Timer function input
–
19
PID disable
–
1A
Accel/decel time selection 2
–
1B
Program lockout
–
1E
Reference sample hold
–
20 to 2F Ext. pump fault
–
30
PID integral reset
–
31
PID integral hold
–
32
Multi-Step Speed
Reference 4
–
34
PID soft starter cancel
–
35
PID input level selection
–
40
Forward run command
(2-Wire sequence)
–
41
Reverse run command
(2-Wire sequence)
–
42
Run command
(2-Wire sequence 2)
–
43
FWD/REV command
(2-Wire sequence 2)
–
47
Node setup
–
Setting
Function
Page
51
Sequence Timer Disable
–
52
Sequence Timer Cancel
–
60
DC Injection Braking command
–
61
External Speed Search
command 1
–
62
External Speed Search
command 2
–
63
Field weakening
–
65
KEB Ride-Thru 1 (N.C.)
–
66
KEB Ride-Thru 1 (N.O.)
–
67
Communications test mode
–
68
High Slip Braking (HSB)
–
6A
Drive enable
–
73
Low City Press
–
75
Up 2 command
–
76
Down 2 command
–
7A
KEB Ride-Thru 2 (N.C.)
–
7B
KEB Ride-Thru 2 (N.O.)
–
80
HAND Mode
–
81
HAND Mode 2
–
83
Alternate Multi-Setpoint (Q1-02)
–
84
Alternate Multi-Setpoint (Q1-03)
–
85
Alternate Multi-Setpoint (Q1-04)
–
88
Volute-Thermostat Normally Open
–
89
Volute-Thermostat Normally Closed
–
8C
Disable Pre-Charge
–
8D
Multi Setpoint 1
–
8E
Multi Setpoint 2
–
8F
Low Water Level
–
90
High Water Level
–
92
Reset Accum
–
95
Remove Drive Disable
–
A8
Secondary PI Disable (N.O.)
–
A9
Secondary PI Disable (N.C.)
–
AA
Secondary PI Inverse Operation
–
AB
Secondary PI Integral Reset
–
AC
Secondary PI Integral Hold
–
AD
Select Secondary PI Parameters
–
AF
Emergency Override Forward Run
–
B0
Emergency Override Reverse Run
–
n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection
The drive has three multi-function output terminals.
lists the functions available for theses terminals using H2-01,
H2-02, and H2-03.
4.6 Basic iQpump Setup and Application Preset Parameters
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
217
4
Start-Up Programming & Operation