U: monitors, U1: operation status monitors, B.15 u: monitors – Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 401: Refer to u1, U1 - 10, U1 - 11

background image

B.15 U: Monitors

Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.

u

U1: Operation Status Monitors

No.

(Addr.

Hex)

Name

LCD Display

Description

Analog

Output Level

Unit

U1-01

(0040)

Frequency Reference

Frequency Ref

Monitors the frequency reference. Display units are determined

by o1-03.

10 V: Max

frequency

0.01 Hz

U1-02

(0041)

Output Frequency

Output Freq

Displays the output frequency. Display units are determined by

o1-03.

10 V: Max

frequency

0.01 Hz

U1-03

(0042)

Output Current

Output Current

Displays the output current.

Note:

The unit is expressed in 1 A for models 4A0930

and 4A1200.

10 V: Drive

rated current

<1>

<2>

U1-04

(0043)

Control Method

Control Method

0: V/f Control

2: OLV Control

No signal output

available

U1-05

(0044)

Motor Speed

Motor Speed

OLV

OLV

OLV

OLV

Displays the motor speed feedback. Display units are

determined by o1-03.

10 V: Max

frequency

0.01 Hz

U1-06

(0045)

Output Voltage

Reference

Output Voltage

Displays the output voltage.

10 V: 200 Vrms

<3>

0.1 Vac

U1-07

(0046)

DC Bus Voltage

DC Bus Voltage

Displays the DC bus voltage.

10 V: 400 V

<3>

1 Vdc

U1-08

(0047)

Output Power

Output kWatts

Displays the output power (this value is calculated internally). 10 V: Drive

capacity

(motor capacity)

kW

<4>

U1-09

(0048)

Torque Reference

Torque Reference

OLV

OLV

OLV

OLV

Monitors the internal torque reference.

10 V: Motor

rated torque

0.1%

U1-10

(0049)

Input Terminal Status

Input Term Sts

Displays the input terminal status.

U1 - 10=

00000000

Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)

1
1
1
1
1
1
1
1

No signal output

available

U1-11

(004A)

Output Terminal

Status

Output Term Sts

Displays the output terminal status.

U1 - 11=

00000000

Multi-Function

Digital Output

(terminal M1-M2)

Digital Output

(terminal M3-M4)

Digital Output

Multi-Function

Multi-Function

Not Used

Fault Relay

(terminal MA-MC closed

MA-MC open)

1

1

1

1

0

(terminal MD-ME-MF)

No signal output

available

B.15 U: Monitors

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

401