Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 177

13.
The pump can be run in HAND (LOCAL) Mode for maintenance purposes by pressing the HAND key while the drive
is stopped. The HAND key acts as a start button. Press the OFF button to stop the drive. Press AUTO to return the
drive to geothermal control. The HAND speed reference can be set in P5-02 (Hand Reference 1). Disable the HAND
key by setting P5-04 to 0 (disabled).
Related Parameters, Faults, and Alarms
No.
Parameter Name
Setting Values
A1-01
Access Level Selection
Default: 2
Range: 0 to 3
A1-03
Initialize Parameters
Default: 0
Range: 0 to 5550; 6008 to 6011; 7770
b1-02
Run Command Selection 1
Default: 0
Range: 0 to 3
E2-01
Motor Rated Current
Default:
Min.: 10% of drive rated current
Max.: 200% of drive rated current
E2-04
Number of Motor Poles
Default: 2
Min.: 2
Max.: 48
P1-03
Feedback Device Scaling
Default: 145.0 PSI
Min.: 0.1
Max.: 6000.0
P1-04
Start / Draw Down Level
Default: 0.0
Min.: -999.9
Max.: 999.9
P1-06
Minimum Pump Speed
Default: 40.0 Hz
Min.: 0.0
Max.: [E1-04]
P1-11
High Feedback Level
Default: 0.0 PSI
Min.: 0.0
Max.: 6000.0
P2-02
Sleep Level
Default: 0.0 Hz
Min.: 0.0
Max.: 6000.0
P4-10
AUTO Mode Operator Run Power Down Storage
Default: 0
Range: 0, 1
P5-02
HAND Speed Reference 1
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
P5-04
HAND Key Function Selection
Default: 1
Range: 0, 1
Q1-01
PID Controller Setpoint 1
Default: 0.0
Min.: 0.0
Max.: 6000.0
Q2-01
Minimum Geothermal Temperature Input
Default: 0.0 °F
Min.: -110.0
Max.: 275.0
Q2-02
Maximum Geothermal Temperature Input
Default: 120.0 °F
Min.: -100.0
Max.: 275.0
Q2-03
Minimum Geothermal Speed
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
Q2-04
Maximum Geothermal Speed
Default: 60.0 Hz
Min.: 0.0
Max.: 400.0
Q2-05
Low Temperature to Run at Maximum Geothermal Speed
Default: 55.0 °F
Min.: -110.0
Max.: 275.0
4.5 iQpump Presets and Functions
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
177
4
Start-Up Programming & Operation