Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 200

Network State
Display
Drive is in Auto Mode, Lag operation and is
holding the speed at the time it made the
switch from being a lead drive to a lag. Speed
is held until P9-07 time expires. The Home
screen will display U1-01 instead of U5-99.
Lag: Fixed Hold
- MODE -
DRV RDY
Home
U1-02=
U1-91=
59.41Hz
99.8PSI
U1-01= 59.41
HZ
Drive is in Auto Mode, Lag operation and is
running at the speed set in P9-06. The Home
Screen will display U1-01 instead of U5-99.
Lag: Fixed P9-06
- MODE -
DRV RDY
Home
U1-02=
U1-91=
55.00Hz
99.9PSI
U1-01= 55.00
HZ
Drive is in AUTO Mode, Lag operation and
is following the speed of the current Lead
drive. The Home screen will display U1-01
instead of U5-99.
Lag: Follow Lead
- MODE -
DRV RDY
Home
U1-02=
U1-91=
51.35Hz
98.9PSI
U1-01= 51.37
HZ
Drive is in AUTO Mode, Lead operation with
Geothermal Enabled. The Home screen will
display U1-01 instead of U5-99
Lead: Geothermal
- MODE -
DRV RDY
Home
U1-02=
U1-80=
44.82Hz
83.6˚F
U1-01= 48.00
HZ
PI Feedback via Network
The Network PI Feedback comes from a drive on the network with a valid analog PI feedback source and can be used as the
primary or secondary feedback source for a networked drive.
Set P9-02 to 0 if a drive has an analog PI feedback device installed and switching to network as a backup is not desired.
if a drive has an analog PI feedback device installed and the network PI feedback is considered as a backup, set P9-02 to 1 for
no alarm message when switched and set P9-02 to 2 for an alarm.
Set P9-02 to 3 if a drive has no analog PI feedback device installed and relies solely on the analog PI feedback of another
networked drive.
Note:
Connect an analog PI feedback device to each drive for best performance.
Related Parameters
No.
Parameter Name
Setting Values
H5-01
Drive Node Address
Default: 1F (Hex)
Min.: 0
Max.: FF
P1-01
Pump Mode
Default: 0
Range: 0, 1, 3
P9-02
Feedback Source
Default: 0
Range: 0 to 3
4.5 iQpump Presets and Functions
200
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide