S3: secondary pi (pi2) control – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 397
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S2-15
(3214)
Sequence Timer 3
Reference Source
Tmr 3 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 3 is active (only applicable when
S2-14 is set to 1 or 2).
0: Operator (d1-01/Q1-01)
1: Operator (d1-02/Q1-02)
2: Operator (d1-03/Q1-03)
3: Operator (d1-04/Q1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
–
S2-16
(3215)
Sequence Timer 4 Start
Time
Tmr 4 Start Time
Sets the start time for timer 4. The value must be set less than
or equal to S2-17.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
–
S2-17
(3216)
Sequence Timer 4 Stop
Time
Tmr 4 Stop Time
Sets the stop time for timer 4. The value must be set greater than
or equal to S2-16.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
–
S2-18
(3217)
Sequence Timer 4 Day
Selection
Tmr 4 Day Sel
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 4 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
–
S2-19
(3218)
Sequence Timer 4
Selection
Tmr 4 Seq Sel
0: Digital out only
1: Run
2: Run - PI Disable
Sets the action that occurs when sequence timer 4 is active.
0: Digital output only
1: Run
2: Run - PI disable
Default: 0
Range: 0 to 2
–
S2-20
(3219)
Sequence Timer 4
Reference Source
Tmr 4 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 4 is active (only applicable when
S2-19 is set to 1 or 2).
0: Operator (d1-01/Q1-01)
1: Operator (d1-02/Q1-02)
2: Operator (d1-03/Q1-03)
3: Operator (d1-04/Q1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
–
<1> Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer.
u
S3: Secondary PI (PI2) Control
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S3-01
(321A) Secondary PI Enable
Selection
PI2 Enable Sel
0: Disabled
1: Always
2: Drive running
3: Motor running
Determines when the secondary PI controller is enabled.
0: Disabled
1: Always
2: Drive running
3: Motor running
Note:
Setting 3 does not run the motor at zero speed,
baseblock, or in DC injection.
Default: 0
Range: 0 to 3
–
S3-02
(321B) Secondary PI User
Display
PI2 UsrDspMaxVal
Sets the scale value of 100% PI input.
Default: 10000
Min.: 0
Max.: 60000
–
B.13 S: Special Application
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
397
B
Parameter List