P1-02: system units, P1-03: feedback device scaling – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 224

n
P1-02: System Units
Selects the base unit in which most drive PID setpoints, scaling, monitors, limits, and faults/alarm levels will be set.
Note:
Set this parameter prior to changing other parameters, as internal scaling is based on P1-02.
No.
Parameter Name
Setting Range
Default
P1-02
System Units
0 to 10; 25, 26
1
Setting 0: No unit
Setting 1: PSI: Pounds per square inch
Setting 2: Pa: Pascals
Setting 3: Bar: Bar
Setting 4: "WC: Inch of water
Setting 5: "Hg: Inch of Mercury
Setting 6: ft: feet
Setting 7: m: meters
Setting 8: °F: Degrees Fahrenheit
Setting 9: °C: Degrees Celsius
Setting 10: Percent
Setting 25: Flow (Use P6-04)
Note:
When using setting 25, the system units are set by parameter P6-04 and the PID feedback is re-routed to come from the flow meter, pulse
input (H6-01 = 5), or analog (H3-0o = 22).
Setting 26: Custom (P1-32 to P1-34)
This setting allows the user to create a custom system unit display with up to three characters. Use parameters P1-32 to P1-34
to make the custom system unit.
The following are the selections available for custom system units:
Setting
Character
Setting
Character
Setting
Character
Setting
Character
20
SPACE
34
4
4F
O
69
I
21
!
35
5
50
P
6A
j
22
“
36
6
51
Q
6B
k
23
#
37
7
52
R
6C
l
24
$
38
8
53
S
6D
m
25
%
39
9
54
T
6E
n
26
&
41
A
55
U
6F
o
27
'
42
B
56
V
70
p
28
(
43
C
57
W
71
q
29
)
44
D
58
X
72
r
2A
*
45
E
59
Y
73
s
2B
+
46
F
5A
Z
74
t
2C
,
47
G
61
a
75
u
2D
-
48
H
62
b
76
v
2E
.
49
I
63
c
77
w
2F
/
4A
J
64
d
78
x
30
0
4B
K
68
e
79
y
31
1
4C
L
66
f
7A
z
32
2
4D
M
67
g
33
3
4E
N
68
h
n
P1-03: Feedback Device Scaling
Sets the feedback device scaling used for the PID controller. This information can be found on the nameplate or specification
sheet and is usually expressed as the maximum output of the device.
For example, a pressure sensor scaling might be 145.0 PSI at 20 mA output and would require setting P1-03 to 145.0 PSI.
Note:
Set this parameter prior to changing other parameters related to the PID feedback, as internal scaling is based on P1-03.
4.6 Basic iQpump Setup and Application Preset Parameters
224
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide