• De-staging will stop the current Lead drive and restore the previous drive as the Lead drive.

Multiplexing Messages

During multiplexing, the drive will display a message when it will be staged in or de-staged out. The message will indicate if

it is being staged in or out and display a countdown timer of how long until the change takes place.
One of the following conditions must be met for de-staging to occur:
• High Feedback Quick De-stage
• Low Feedback Quick De-stage
• Normal De-stage
• Low Water Level De-stage
• Suction Pressure De-stage

Drive Run Order

U9-04, Running Queue No:
• Shows the position in the iQpump MEMOBUS running queue.
• U9-04 = 0 for pumps that are not running.
• U9-04 = 1 on the first pump that came on and is still running.
• U9-04 = 2 on the second pump that came on and is still running.
• U9-04 = the number of pumps running for the current Lead drive.

Multiplex Status Display

Table 4.9 Multiplex Status Display

Network State

Display

Drive is not able to accept commands from

the iQpump MEMOBUS network because

the drive is not in AUTO Mode run.

Pump Off Network

- MODE -

DRV RDY

Home

U1-02=

U1-91=

0.00Hz

62.8PSI

U5-99= 100.0

PSI

Drive is in AUTO Mode and waiting for a run

command from the iQpump MEMOBUS

network.

Wait for Net Cmd

- MODE -

DRV RDY

Home

U1-02=

U1-91=

0.00Hz

62.8PSI

U5-99= 100.0

PSI

Drive is in AUTO Mode, Lead operation and

is currently regulating the system using PI

control.

Lead: Setpoint

- MODE -

DRV RDY

Home

U1-02=

U1-91=

52.38Hz

62.8PSI

U5-99= 100.0

PSI

4.5 iQpump Presets and Functions

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

199

4

Start-Up Programming & Operation