beautypg.com

Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 27

background image

4000

600

0

60

400

Drive Capacity (kVA)

Power Supply

Capacity (kVA)

Power supply harmonics
reactor required

Reactor
unnecessary

Figure i.1 Installing a Reactor

Single-Phase Input Selection

The drive is capable of single phase input.

Refer to Main Circuit Connection Diagram on page 121

for connection diagrams

and

Refer to Single-Phase Derating on page 317

for application instructions and drive current ratings.

Drive Capacity

For specialized motors, make sure that the motor rated current is less than the rated output current for the drive.
When running more than one motor in parallel from a single drive, the capacity of the drive should be larger than [total motor

rated current × 1.1].

n

Installation

Enclosure Panels

Keep the drive in a clean environment by installing the drive in an enclosure panel or selecting an installation area free of

airborne dust, lint, and oil mist. Be sure to leave the required space between drives to provide for cooling, and take proper

measures so the ambient temperature remains within allowable limits and keep flammable materials away from the drive.

Yaskawa offers protective designs for drives that must be used in areas subjected to oil mist and excessive vibration. Contact

Yaskawa or your Yaskawa agent for details.

Installation Direction

NOTICE: Install the drive upright as specified in the manual.

Refer to Mechanical Installation on page 36

for more information on

installation. Failure to comply may damage the drive due to improper cooling.

n

Settings

Upper Limits

NOTICE: The drive is capable of running the motor up to 400 Hz. Be sure to set the upper limit for the frequency of the drive to prevent the

possible danger of accidentally operating equipment at higher than rated speed. The default setting for the maximum output frequency is

60 Hz.

Lower Limits

NOTICE: Many pumps have a minimum safe operating speed. Be sure to properly set the minimum pump speed in to protect the pump

from damage.

DC Injection Braking

NOTICE: Excessive current during DC Injection Braking and excessive duration of DC Injection Braking can cause motor overheat.

Acceleration/Deceleration Times

Acceleration and deceleration times are affected by the amount of torque generated by the motor, the load torque, and the

inertia moment. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as

long as the Stall Prevention function is in operation.

n

General Handling

Wiring Check

NOTICE: Do not connect power supply lines to output terminals U/T1, V/T2, or W/T3. Failure to comply will destroy the drive. Be sure to

perform a final check of all sequence wiring and other connections before turning on the power and also check for short circuits on the

control terminals, which may damage the drive.

Selecting a Circuit Breaker or Circuit Interrupter

Yaskawa recommends installing a Ground Fault Circuit Interrupter (GFCI) to the power supply side. The GFCI should be

designed for use with AC drives (e.g., Type B according to IEC 60755).
Select a Molded Case Circuit Breaker (MCCB) or GFCI with a rated current 1.5 to 2 times higher than the drive rated input

current to avoid nuisance trips caused by harmonics in the drive input current.

i.2 General Safety

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

27