U1 - 92 – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 403

No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U1-80
(0B9B)
Geothermal
Temperature Input
Geothermal Temp
Displays the geothermal temperature input after the gain and
bias have been applied. This temperature is used by the
Geothermal Function to determine the proper frequency at
which to run the drive.
This monitor is internally limited to -999.9 °F to +999.9 °F.
No signal output
available
0.1 °F
U1-83
(0B9E) Flow Rate
Flow Rate
Displays the flow rate based on the pulse input frequency or the
analog voltage (flow rate input) and parameters P6-01 and
P6-04.
A 2-second first order filter will be applied to this monitor.
Full scale: P6-01 dep. on
P6-04
U1-84
(0B9F)
Accumulation Level -
Millions
Volume * 1000000
Displays the recorded volume from the flow meter (pulse input
or analog voltage).
Total volume is calculated as follows:
Total Volume = (U1-84 * 1000000) + (U1-85 * 1000) + U1-86
+ U1-87
No signal output
available
dep. on
P6-16
U1-85
(0BA0)
Accumulation Level -
Thousands
Volume * 1000
U1-86
(0BA1)
Accumulation Level -
Ones
Volume * 1
U1-87
(0BA2)
Accumulation Level -
Decimal
Volume * 0.0001
U1-90
(0BA5) Pump Setpoint
Pump Setpoint
Displays the PID Setpoint.
No signal output
available
dep. on
P1-02
U1-91
(0BA6) Pump Feedback
Pump Feedback
Displays the PID Feedback.
No signal output
available
dep. on
P1-02
U1-92
(0BA7) Pump Status
Pump Status
Displays Pump Running Status.
U1 - 92=
00000000
Drive
Pump 2
Pump 3
Pump 4
Pump 5
Pump 6
Not used
Not used
1
1
1
1
1
1
0
0
No signal output
available
–
U1-93
(0BA8)
Total Setpoint
Compensation
Total SP Comp.
Displays the total absolute Setpoint Compensation.
No signal output
available
dep. on
P1-02
U1-94
(0BA9) Motor Speed
Motor Speed
Displays the absolute value of the output frequency (U1-02)
converted to RPM.
No signal output
available
1 RPM
U1-97
(0BAC) Water Level
Water Level
Displays the amount of water above the water level sensor.
Full scale:
10 V = Q4-02
0.1 ft.
U1-98
(0BAD) Suction Pressure
Suction Pressure
Displays the amount of suction pressure.
Full scale:
10 V = Q5-02
0.1 PSI
or ”Hg
U1-99
(0BAE) Anti-No-Flow Timer
ANF Timer
The Anti-No-Flow reduces the output frequency when this
value reaches the P2-24 setting.
No signal output
available
0.1 s
<1> Display is in the following units:
2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0007 to 5A0017: 0.01 A units.
2A0056 to 2A0415, 4A0031 to 4A0675, and 5A0022 to 5A0242: 0.1 A units.
4A0930 and 4A1200: 1 A units.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is higher than 11 kW.
<5> Available in drive software versions PRG: 8551 and later.
B.15 U: Monitors
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
403
B
Parameter List