Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 244

HOA Keypad Display
Fault Name
EF0
Option Card External Fault
An external fault condition is present.
Cause
Possible Solution
An external fault was received from the
PLC and F6-03 is set to a value other than
3.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
Problem with the PLC program
Check the PLC program and correct problems.
HOA Keypad Display
Fault Name
EF1
Pump Fault (input terminal S1)
External fault at multi-function input terminal S1.
EF2
Pump Fault (input terminal S2)
External fault at multi-function input terminal S2.
EF3
Pump Fault (input terminal S3)
External fault at multi-function input terminal S3.
EF4
Pump Fault (input terminal S4)
External fault at multi-function input terminal S4.
EF5
Pump Fault (input terminal S5)
External fault at multi-function input terminal S5.
EF6
Pump Fault (input terminal S6)
External fault at multi-function input terminal S6.
EF7
Pump Fault (input terminal S7)
External fault at multi-function input terminal S7.
EF8
Pump Fault (input terminal S8)
External fault at multi-function input terminal S8.
Cause
Possible Solution
An external device tripped an alarm
function
Remove the cause of the external fault and reset the fault.
Wiring is incorrect
• Properly connect the signal lines to the terminals assigned for external fault detection
(H1-oo = 20 to 2B).
• Reconnect the signal line.
Multi-function contact input setting is
incorrect
• Check for unused terminals set for H1-oo = 20 to 2B (External Fault).
• Change the terminal settings.
HOA Keypad Display
Fault Name
Err
EEPROM Write Error
Data cannot be written to the EEPROM
Cause
Possible Solution
Noise has corrupted data while writing to
the EEPROM
• Press “ENTER” on the digital operator.
• Correct the parameter setting.
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Hardware problem
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
FAn
Internal Fan Fault
Fan or magnetic contactor failure
Cause
Possible Solution
5.2 Fault Detection
244
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide