B.8 L: Protection Function
L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, and other types of hardware protection.
u
L1: Motor Protection
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
L1-01
(0480)
Motor Overload
Protection Selection
Mtr OL Charact
0: OL1 Disabled
1: VT Motor
2: CT Motor
3: Vector Motor
6: 50Hz VT Motor
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
6: General purpose motor (50 Hz)
The drive may not be able to provide protection when using
multiple motors, even if overload is enabled in L1-01. Set L1-01
to 0 and install separate thermal relays to each motor.
Default: 1
Range: 0 to 3; 6
–
L1-02
(0481)
Motor Overload
Protection Time
MOL Time Const
Sets the motor thermal overload protection (oL1) time.
Default: 1.0 min
Min.: 0.1
Max.: 5.0
–
L1-03
(0482)
Motor Overheat Alarm
Operation Selection
(PTC input)
Mtr OH Alarm Sel
0 : Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm only
Sets operation when the motor temperature analog input (H3-02,
H3-10, or H3-06 = E) exceeds the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in
C1-09)
3: Alarm only (“oH3” will flash)
Default: 3
Range: 0 to 3
–
L1-04
(0483)
Motor Overheat Fault
Operation Selection
(PTC input)
Mtr OH Fault Sel
0 : Ramp to Stop
1: Coast to Stop
2: Fast-Stop
Sets stopping method when the motor temperature analog input
(H3-02, H3-10, or H3-06 = E) exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in
C1-09)
Default: 1
Range: 0 to 2
–
L1-05
(0484)
Motor Temperature
Input Filter Time (PTC
input)
Mtr Temp Filter
Adjusts the filter for the motor temperature analog input (H3-02,
H3-10, or H3-06 = E).
Default: 0.20 s
Min.: 0.00
Max.: 10.00
–
L1-13
(046D)
Continuous
Electrothermal
Operation Selection
Mtr OL Mem Sel
0: Disabled
1: Enabled
2: Enabled(RTC)
0: Disabled
1: Enabled
2: Enabled (RTC)
Default: 1
Range: 0 to 2
–
L1-15
(0440)
Motor 1 Thermistor
Selection (NTC)
M1 OH5 Fault Sel
0: Disabled
1: Enabled
Note:
This parameter is only available in models
4A0930 and 4A1200.
Default: 0
Range: 0, 1
–
L1-16
(0441)
Motor 1 Overheat
Temperature
M1 OH5 level
Sets the temperature for motor 1 that triggers an overheat fault
(oH5).
Note:
This parameter is only available in models
4A0930 and 4A1200.
Default: 120 °C
Min.: 50
Max.: 200
–
L1-17
(0442)
Motor 2 Thermistor
Selection (NTC)
M2 OH5 Fault Sel
0: Disabled
1: Enabled
Note:
This parameter is only available in models
4A0930 and 4A1200.
Default: 0
Range: 0, 1
–
L1-18
(0443)
Motor 2 Overheat
Temperature
M2 OH5 level
Sets the temperature for motor 1 that triggers an overheat fault
(oH5).
Note:
This parameter is only available in models
4A0930 and 4A1200.
Default: 120 °C
Min.: 50
Max.: 200
–