5.2 Fault Detection
u
Fault Displays, Causes, and Possible Solutions
Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal MA-MB-MC.
Remove the cause of the fault and manually clear the fault before attempting to run the drive again.
Table 5.2 Detailed Fault Displays, Causes, and Possible Solutions
HOA Keypad Display
Fault Name
ACCUM
Accum Level
Accumulated Level Fault
The total volume of water flow measured over time by the flow meter has exceeded the fault level setting.
Cause
Possible Solution
The accumulated level has exceeded the
values set in P6-11 to P6-14. This is only
effective when P6-15, Accumulated
Behavior is set to 2 (fault with manual
monitor reset) or 3 (fault with automatic
monitor reset.
Set the Accumulated Level fault characteristics in P6-11 to P6-14 and P6-16.
Drive response to this condition is controlled by P6-15, Accumulated Behavior.
Auto-restart of this fault is controlled by P6-15, Accumulated Behavior and P6-05, Flow Accumulation Reset.
HOA Keypad Display
Fault Name
AJF
Anti-Jam Fault
Anti-Jam Fault
Cause
Possible Solution
The drive was not able to clear debris from
the impeller in fewer than the number of
attempts set in P7-02. This is only effective
when P7-01, Anti-jam Operation is set to 1
(enabled).
• Check for proper pump operation. Remove debris from the pump impeller.
• Set the Anti-jam fault characteristics in P7-02 to P7-08.
• Drive response to this condition is controlled by P7-01, Anti-jam Operation Selection.
HOA Keypad Display
Fault Name
bAT
Digital Operator Battery Voltage Low
Cause
Possible Solution
The digital operator battery is low
Replace the digital operator battery.
HOA Keypad Display
Fault Name
boL
Braking Transistor Overload Fault
The braking transistor reached its overload level.
Cause
Possible Solution
The wrong braking resistor is installed
Select the correct braking resistor.
HOA Keypad Display
Fault Name
bUS
Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the run command frequency reference is assigned to an option card.
Cause
Possible Solution
No signal was received from the PLC
• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.
Faulty communications wiring or an
existing short circuit
Communication data error occurred due to
noise
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge absorbers if
necessary.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or the drive
input power side.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power
supply input.
The option card is damaged
Replace the option card if there are no problems with the wiring and the error continues to occur.
The option card is not properly connected
to the drive
• The connector pins on the option card do not line up properly with the connector pins on the drive.
• Reinstall the option card.