HOA Keypad Display

Error Name

End7

No-Load Current Alarm

Cause

Possible Solutions

The entered no-load current value was outside the

allowable range.

Check and correct faulty motor wiring.

Auto-Tuning results were less than 5% of the

motor rated current.

Double-check the data entered for the Auto-Tuning process.

HOA Keypad Display

Error Name

Er-01

Motor Data Error

Cause

Possible Solutions

Motor data or data entered during Auto-Tuning

was incorrect

.

• Check that the motor data entered to T1 parameters matches motor nameplate input before Auto-

Tuning.

• Restart Auto-Tuning and enter the correct information.

Motor output power and motor-rated current

settings (T1-02 and T1-04) do not match.

• Check the drive and motor capacities.
• Correct the settings of parameters T1-02 and T1-04.

Motor rated current and detected no-load current

are inconsistent.

• Check the motor rated current and no-load current.
• Correct the settings of parameters T1-04 and E2-03.

HOA Keypad Display

Error Name

Er-02

Minor Fault

Cause

Possible Solutions

An alarm was triggered during Auto-Tuning.

Exit the Auto-Tuning menu, check the alarm code, remove the alarm cause, and repeat Auto-Tuning.

HOA Keypad Display

Error Name

Er-03

STOP Button Input

Cause

Possible Solutions

Auto-Tuning canceled by pressing STOP button. Auto-Tuning did not complete properly. Restart Auto-Tuning.

HOA Keypad Display

Error Name

Er-04

Line-to-Line Resistance Error

Cause

Possible Solutions

Motor data entered during Auto-Tuning was

incorrect.

• Make sure the data entered to the T1 parameters match the information written on the motor

nameplate.

• Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the

parameter setting range or the tuning process took

too long.

Check and correct faulty motor wiring.

Faulty motor cable or cable connection.

HOA Keypad Display

Error Name

Er-05

No-Load Current Error

Cause

Possible Solutions

Motor data entered during Auto-Tuning was

incorrect.

• Make sure the data entered to the T1 parameters match the information written on the motor

nameplate.

• Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the

parameter setting range or the tuning process took

too long.

• Check and correct faulty motor wiring.
• Perform Rotational Auto-Tuning.

The load was too high during Rotational Auto-

tuning.

• Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be

uncoupled make sure the load is lower than 30%.

• If a mechanical brake is installed, make sure it is fully lifted during tuning.

5.5 Auto-Tuning Fault Detection

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

279

5

Troubleshooting