L3: stall prevention – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 362

No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
L2-10
(048E)
KEB Detection Time
(Minimum KEB Time) KEB Detect Time
Sets the time to perform KEB Ride-Thru.
Default: 50 ms
Min.: 0
Max.: 2000
–
L2-11
(0461)
DC Bus Voltage
Setpoint during KEB
KEB DC Bus Level
Sets the desired value of the DC bus voltage during KEB Ride-
Thru.
Default:
<2>
[E1-01] × 1.22
Min.: 150 Vdc
Max.: 400 Vdc
<5>
–
L2-29
(0475)
KEB Method Selection
KEB Mode Sel
0: Single Mode KEB1
1: Single Mode KEB2
2: System Mode
KEB1
3: System Mode
KEB2
0: Single Drive KEB Ride-Thru 1
1: Single Drive KEB Ride-Thru 2
2: System KEB Ride-Thru 1
3: System KEB Ride-Thru 2
Default: 0
Range: 0 to 3
–
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but
set the value below 1040 Vdc (overvoltage protection level).
u
L3: Stall Prevention
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
L3-01
(048F)
Stall Prevention
Selection during
Acceleration
StallP Accel Sel
0: Disabled
1: General purpose
2: Intelligent
0: Disabled.
1: General purpose. Acceleration is paused as long as the current
is above the L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without
exceeding the L3-02 level.
Default: 1
Range: 0 to 2
–
L3-02
(0490)
Stall Prevention Level
during Acceleration
StallP Accel Lvl
Used when L3-01 = 1 or 2. 100% is equal to the drive rated
current.
Default:
<1>
Min.: 0%
Max.: 150%
<1>
–
L3-03
(0491)
Stall Prevention Limit
during Acceleration
StallPAcc LowLim
Sets Stall Prevention lower limit during acceleration when
operating in the constant power range. Set as a percentage of
drive rated current.
Default: 50%
Min.: 0
Max.: 100
–
L3-04
(0492)
Stall Prevention
Selection during
Deceleration
StallP Decel Sel
0: Disabled
1: General purpose
2: Intelligent
3: StallP +Resistor
4: High Flux Brake
5: High Flux Brake2
0: Disabled. Deceleration at the active deceleration rate. An ov
fault may occur.
1: General purpose. Deceleration is paused when the DC bus
voltage exceeds the Stall Prevention level.
2: Intelligent. Decelerate as fast as possible while avoiding ov
faults.
3: Stall Prevention with braking resistor. Stall Prevention during
deceleration is enabled in coordination with dynamic braking.
4: Overexcitation Deceleration. Decelerates while increasing
the motor flux.
5: Overexcitation Deceleration 2. Adjust the deceleration rate
according to the DC bus voltage.
Note:
Setting 3 is not available in models 4A0930 and
4A1200.
Default: 0
Range: 0 to 5
–
L3-05
(0493)
Stall Prevention
Selection during Run
StallP Run Sel
0: Disabled
1: Decel time
2: Decel time 2
0: Disabled. Drive runs at a set frequency. A heavy load may
cause speed loss.
1: Decel time 1. Uses the deceleration time set to C1-02 while
Stall Prevention is performed.
2: Decel time 2. Uses the deceleration time set to C1-04 while
Stall Prevention is performed.
Default: 0
Range: 0 to 2
–
L3-06
(0494)
Stall Prevention Level
during Run
StallP Run Level
V/f
V/f
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive
rated current.
Default:
<1>
Min.: 30%
Max.: 150%
<1>
–
B.8 L: Protection Function