HOA Keypad Display
Fault Name
HISUC
High Suction
High Section Pressure
Cause
Possible Solution
The suction pressure has fallen below the
level set in Q5-12 for longer than the time
set in Q5-13. This is only effective when
Q5-14, High Suction Pressure Behavior
Select is set to 2 (fault).
• Reduce the system pressure.
• Set the High Suction Pressure fault characteristics in Q5-12, Q5-13, and Q5-18.
• Drive response to this condition is controlled by Q5-14, High Suction Pressure Behavior Select.
• Auto-restart of this fault is controlled by Q5-14, High Suction Pressure Behavior Select and Q5-15, Suction
Pressure Auto-restart Time.
HOA Keypad Display
Fault Name
HWL
High Water Level
The “High Water Level” digital input is active (H1-0o = 90).
Cause
Possible Solution
The Low Water Level switch is activated or
P1-31, High Water Digital Input
Configuration, is programmed incorrectly.
Lower the water level and/or adjust the High Water Level switch.
HOA Keypad Display
Fault Name
LF
Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.
Cause
Possible Solution
The output cable is disconnected
• Check for wiring errors and properly connect the output cable.
• Correct the wiring.
The motor winding is damaged
• Check the resistance between motor lines.
• Replace the motor if the winding is damaged.
The output terminal is loose
• Apply the tightening torque specified in this manual to fasten the terminals.
Gauges and Tightening Torque on page 134
for details.
The rated current of the motor being used
is less than 5% of the drive rated current
Check the drive and motor capacities.
An output transistor is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
A single-phase motor is being used
The drive cannot operate a single phase motor.
HOA Keypad Display
Fault Name
LF3
<1>
Power Unit Output Phase Loss 3
• Phase loss occurred on the output side
• Setting L8-78 to 1 enables Power Unit Output Phase Loss Protection
Cause
Possible Solution
The gate drive board in the power unit is
damaged.
Cycle the power supply. If the fault continues to occur, replace the gate drive board or the drive. Contact
Yaskawa or a Yaskawa representative for instructions on replacing the gate drive board.
Cable to the current detection circuit in the
power unit is damaged or not connected
properly.
Check for incorrect wiring and correct any wiring mistakes.
Cable between the output rector and the
power unit is loose or not connected.
Contact Yaskawa or your nearest sales representative for instructions.
<1> Detected in models 4A0930 and 4A1200.
HOA Keypad Display
Fault Name
LFB
Low Feedback
The feedback signal is too low.
Cause
Possible Solution
5.2 Fault Detection
246