Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 353

H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function
LCD Display
Description
Page
15
Frequency detection 3
Freq Detect 3
Closed: When the drive output frequency is less than or equal to the value in L4-03
±L4-04.
–
16
Frequency detection 4
Freq Detect 4
Closed: When the output frequency is greater than or equal to the value in L4-03
±L4-04.
–
17
Torque detection 1
(N.C.)
Trq Det 1 N.C.
Open: Overtorque or undertorque has been detected.
–
18
Torque detection 2
(N.O.)
Trq Det 2 N.O.
Closed: Overtorque or undertorque has been detected.
19
Torque detection 2
(N.C.)
Trq Det 2 N.C.
Open: Overtorque or undertorque has been detected.
–
1A
During reverse
Reverse Dir
Closed: Drive is running in the reverse direction.
–
1B
During baseblock
(N.C.)
BaseBlk 2
Open: Drive has entered the baseblock state (no output voltage).
–
1E
Restart enabled
Dur Flt Restart
Closed: An automatic restart is performed
–
1F
Motor overload alarm
(oL1)
Overload (OL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers
this alarm.
–
20
Drive overheat pre-
alarm (oH)
OH Prealarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
–
22
Mechanical weakening
detection
MechFatigue(OL5)
Closed: Mechanical weakening detected.
–
2F
Maintenance period
Maintenance
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
may require maintenance.
–
30
During torque limit
Torque Limit
OLV
OLV
OLV
OLV
Closed: The torque limit has been reached.
–
37
During frequency
output
During RUN 2
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is
not being performed).
–
38
Drive enabled
Drive Enable
Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)
–
39
Watt hour pulse output Watt-hour Pulse
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
the kWh count.
–
3C
LOCAL/REMOTE
status
Local
Open: REMOTE
Closed: LOCAL
–
3D
During speed search
During SpdSrch
Closed: Speed Search is being executed.
–
3E
PID feedback low
PID Feedback Low
Closed: PID feedback level is too low.
–
3F
PID feedback high
PID FeedbackHigh
Closed: The PID feedback level is too high.
–
4A
During KEB Ride-Thru During KEB
Closed: KEB Ride-Thru is being performed.
–
4C
During fast stop
During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input
terminals.
–
4D
oH Pre-alarm time limit OH Pre-Alarm
Closed: oH pre-alarm time limit has passed.
–
4E
Braking transistor fault
(rr)
Brk Trans Fault
Closed: The built-in dynamic braking transistor failed.
Note:
This setting is not available in models 2A0169 to 2A0415 and
4A0088 to 4A1200.
–
4F
Braking resistor
overheat (oH)
BrkResistOvHeat
Closed: The dynamic braking resistor has overheated.
Note:
This setting is not available in models 2A0169 to 2A0415 and
4A0088 to 4A1200.
–
50
Waiting to Run
Waiting for Run
Closed: b1-11 Back Spin Timer is active.
–
51
Sequence timer 1
SeqTimer Disable
Closed: Sequence timer 1 is active.
–
52
Sequence timer 2
SeqTimer Cancel
Closed: Sequence timer 2 is active.
–
53
Sequence timer 3
Sequence timer 3
Closed: Sequence timer 3 is active.
–
54
Sequence timer 4
Sequence Timer 4
Closed: Sequence timer 4 is active.
–
58
Underload detection
UL6
Closed: Underload is detected.
–
60
Internal cooling fan
alarm
Fan Alrm Det
Closed: Internal cooling fan alarm
–
B.7 H Parameters: Multi-Function Terminals
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
353
B
Parameter List