b6: Dwell Function
No.
(Addr.
Hex)
Name
Description
Values
Page
b6-01
(01B6) Dwell Reference at Start Dwell Ref @Start
Parameters b6-01 and b6-02 set the frequency to hold and the
time to maintain that frequency at start.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
–
b6-02
(01B7) Dwell Time at Start
Dwell Time @Start
Default: 0.0 s
Min.: 0.0
Max.: 10.0
–
b6-03
(01B8) Dwell Reference at Stop Dwell Ref @Stop
Parameters b6-03 and b6-04 set the frequency to hold and the
time to maintain that frequency at stop.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
–
b6-04
(01B9) Dwell Time at Stop
Dwell Time @Stop
Default: 0.0 s
Min.: 0.0
Max.: 10.0
–
u
b8: Energy Saving
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
b8-01
(01CC)
Energy Saving Control
Selection
Energy Save Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
b8-02
(01CD) Energy Saving Gain
Energy Save Gain
OLV
OLV
OLV
OLV
Sets the gain used for Energy Saving.
Default: 0.7
Min.: 0.0
Max.: 10.0
–
b8-03
(01CE) Energy Saving Control
Filter Time Constant
Energy Save F.T
OLV
OLV
OLV
OLV
Sets a time constant for Energy Saving.
Default:
<1>
Min.: 0.00 s
Max.: 10.00 s
–
b8-04
(01CF)
Energy Saving
Coefficient Value
Energy Save COEF
V/f
V/f
Determines the level of maximum motor efficiency. Setting
range is 0.0 to 2000.0 for drives 3.7 kW and smaller. The display
resolution depends on the rated output power of the drive.
Default:
<1> <2>
Min.: 0.00
Max.: 655.00
–
b8-05
(01D0)
Power Detection Filter
Time
kW Filter Time
V/f
V/f
Sets a time constant filter for output power detection.
Default: 20 ms
Min.: 0
Max.: 2000
–
b8-06
(01D1)
Search Operation
Voltage Limit
Search V Limit
V/f
V/f
Sets the limit for the voltage search operation as a percentage of
the motor rated voltage.
Default: 0%
Min.: 0
Max.: 100
–
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
B.2 b: Application