No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P6-18
(0D6F) High Flow Detection
Delay Time
High Flow Time
Sets the length of time that the flow rate must be above the level
set in P6-17 to detect a High Flow condition.
Default: 10 s
Min.: 1
Max.: 6000
–
P6-19
(0D70) High Flow Select
High Flow Sel
0: No Display
1: Alarm Only
2: Fault
3: Restart (L5-04)
Sets drive behavior when a High Flow condition is detected.
0: No display
1: Alarm only
2: Fault
3: Auto-restart (time set by L5-04)
Default: 1
Range: 0 to 3
–
P6-20
(0D71)
<3>
Accumulator Stopping
Method Selection
Accum Stop Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
Selects how the drive stops when the Flow Accumulator has
reached its target level (P6-11 to P6-14). Effective only when
P6-15 (Accum Behavior) is set for Fault or Stop (selections 2 to
5).
Default: 1
Range: 0 to 2
–
P6-31
(0D7C)
<3>
Set Accumulation Level
- Millions
SetAccumLvl*10000
00
Parameters P6-31 to P6-34 set the stored accumulated volume.
Level = (P6-31 * 1000000) + (P6-32 * 1000) + P6-33 + P6-34.
Value is accepted when P6-05 = 8880, after which it resets to 0.
Default: 0
<2>
Min.: 0
Max.: 65535
–
P6-32
(0D7D)
<3>
Set Accumulation Level
- Thousands
SetAccumLvl * 1000
Default: 0
<2>
Min.: 0
Max.: 999
–
P6-33
(0D7E)
<3>
Set Accumulation Level
- Ones
SetAccumLvl * 1
Default: 0
<2>
Min.: 0
Max.: 999
–
P6-34
(0D7F)
<3>
Set Accumulation Level
- Decimal
SetAccumLvl *0.0001
Default: 0.0000
<2>
Min.: 0.0000
Max.: 0.9999
–
<1> Unit text is set by P6-04, Water Flow Units.
<2> Unit text is set by P6-16, Flow Meter Accumulator Units Select.
<3> Available in drive software versions PRG: 8551 and later.
u
P7: Anti-Jam
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P7-01
(0D90)
Anti-Jam Operation
Selection
Anti-Jam Sel
0: Disabled
1: Enabled
Enables and disables the anti-jam function.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
–
P7-02
(0D91) Anti-Jam Cycle Count AJ Cycle Count
Sets the maximum number of cycles that will be attempted
before triggering and Anti-Jam fault.
Default: 1
Min.: 1
Max.: 100
–
P7-03
(0D92) Anti-Jam Detection
Current Level
AJ Det I @Start
Sets the current level at start that will trigger the anti-jam
function.
Set as a percentage of the motor rated current.
Default: 120%
Min.: 50
Max.: 200
–
P7-04
(0D93) Anti-Jam Detection
Time at Start
AJ Det Tm@Start
Sets the length of time that current must rise above the level set
in P7-03 to trigger the anti-jam function.
Default: 0.3 s
Min.: 0.1
Max.: 2.0
–
P7-05
(0D94) Anti-Jam During Run
Current
AJ Det I @Run
Sets the current level during run that will trigger the anti-jam
function.
Set as a percentage of motor rated current.
Setting this parameter to 0 will disable anti-jam during run.
Default: 0%
Min.: 0
Max.: 200
–
P7-06
(0D95) Anti-Jam During Run
Time
AJ Det Tm @Run
Sets the length of time that the current must rise above the level
set in P7-05 to trigger the anti-jam function.
Restricted to simplex only.
Default: 0.3 s
Min.: 0.1
Max.: 2.0
–
P7-07
(0D96) Anti-Jam Frequency
Reference
AJ Freq Ref
Sets the maximum speed allowed when the anti-jam function is
active.
Default: 25.00
Hz
Min.: 0.00
Max.: 400.00
–
B.11 P: Pump Parameters
384
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide