HOA Keypad Display

Minor Fault Name

PoC

Pump Over Cycle

Cause

Possible Solution

The pump has exceeded the number of

cycles set in P2-10 in the time set in P2-11

and P2-12 is set to 1 (alarm).

• Set the Pump Over Cycle alarm characteristics in P2-10 and P2-11.
• Drive response to this condition is controlled by P2-12, Over Cycling Mode.

HOA Keypad Display

Minor Fault Name

R-DNE-So

Remote Drive Disable

Cause

Possible Solution

Terminal So (H1-0o = 95) has been

closed for the time set in P4-26, Remote

Drive Disable On-Delay, when P4-25,

Remote Drive Disable Selection, was set to

0 (N.O.).

Remove conditions causing the terminal to close.

Terminal So (H1-0o = 95) has been open

for the time set in P4-26, Remote Drive

Disable On-Delay, when P4-25, Remote

Drive Disable Selection, was set to 1

(N.C.).

Remove conditions causing the terminal to open.

HOA Keypad Display

Minor Fault Name

rUn

Motor Switch during Run
A command to switch motors was entered during run.

Cause

Possible Solution

A motor switch command was entered

during run.

Change the operation pattern so that the motor switch command is entered while the drive is stopped.

HOA Keypad Display

Minor Fault Name

SE

MEMOBUS/Modbus Communication Test Mode Error

Note:

This alarm will not trigger a multi-function output terminal that is set for alarm output

(H2-oo = 10).

Cause

Possible Solution

A digital input set to 67H (MEMOBUS/

Modbus test) was closed while the drive

was running.

Stop the drive and run the test again.

HOA Keypad Display

Minor Fault Name

SPL

Suction Pressure Loss

Suction Pressure Loss
Wire-break detection for suction pressure.

Cause

Possible Solution

An analog input programmed for setting 23

“WaterLvl/Suction” has dropped below 3

mA or risen above 21 mA for longer than 1

second.

Repair pressure sensor or wiring.

Digital Operator Display

Minor Fault Name

THo

<1>

Thermistor Disconnect
The thermistor used to detect motor temperature has become disconnected.

Cause

Possible Solutions

The motor thermistor is not connected

properly.

Check the thermistor wiring.

<1> Detected in models 4A0930 and 4A1200.

HOA Keypad Display

Minor Fault Name

TrPC

IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.

Cause

Possible Solution

IGBTs have reached 90% of their expected

performance life.

Replace the drive.

5.3 Alarm Detection

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

271

5

Troubleshooting