Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 254

Improper parameters related to Speed
Search (including Speed Search after a
momentary power loss and after a fault
restart)
• Check the settings for Speed Search-related parameters.
• Enable Speed Search restart function (b3-19 greater than or equal to 1 to 10).
• Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03 respectively).
• Perform Stationary Auto-Tuning for line-to-line resistance and then set b3-14 to 1 to enable Speed
Estimation Speed Search.
Drive input power voltage is too high
• Check the voltage.
• Lower drive input power voltage within the limits listed in the specifications.
The braking transistor or braking resistor
are wired incorrectly
• Check braking transistor and braking resistor wiring for errors.
• Properly rewire the braking resistor device.
Drive fails to operate properly due to noise
interference
• Review the list of possible solutions provided for controlling noise.
• Review the section on handling noise interference and check the control circuit lines, main circuit lines,
and ground wiring.
Load inertia is set incorrectly
• Check the load inertia settings when using KEB, overvoltage suppression, or Stall Prevention during
deceleration.
• Adjust the load inertia ratio in L3-25 to better match the load.
Motor hunting occurs
• Adjust the parameters that control hunting.
• Set the gain for Hunting Prevention (n1-02).
• Adjust the AFR time constant (n2-02 and n2-03).
HOA Keypad Display
Fault Name
PF
Input Phase Loss
Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when
L8-05 is set 1 (enabled).
Cause
Possible Solution
There is phase loss in the drive input power
• Check for wiring errors in the main circuit drive input power.
• Correct the wiring.
There is loose wiring in the drive input
power terminals
• Ensure the terminals are tightened properly.
• Apply the tightening torque as specified in this manual.
Refer to Main Circuit Wire Gauges and
There is excessive fluctuation in the drive
input power voltage
• Check the voltage from the drive input power.
• Review the possible solutions for stabilizing the drive input power.
There is poor balance between voltage
phases
Stabilize drive input power or disable phase loss detection.
The main circuit capacitors are worn out
• Check the maintenance time for the capacitors (U4-05).
• Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor, contact
Yaskawa or a Yaskawa representative.
Check for problems with the drive input power. If drive input power appears normal but the alarm continues
to occur, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.
HOA Keypad Display
Fault Name
PoC
Pump Over Cycle
Cause
Possible Solution
The pump has exceeded the number of
cycles set in P2-10 in the time set in P2-11
and P2-12 is set to 2 (fault).
• Set the Pump Over Cycle fault characteristics in P2-10 and P2-11.
• Drive response to this condition is controlled by P2-12, Over Cycling Mode.
• Auto-restart of this fault is controlled by L5-52, Pump Over Cycle Fault Retry Selection.
• Set the Pump Over Cycle automatic setpoint compensation in P2-12, Over Cycling Mode, P2-13, Setpoint
Compensation, and P2-14, Maximum Setpoint Compensation.
HOA Keypad Display
Fault Name
rF
Braking Resistor Fault
The resistance of the braking resistor is too low.
Cause
Possible Solution
The proper braking resistor option has not
been installed
Select a braking resistor option that it fits the drive braking transistor specification.
A regenerative converter, regenerative unit,
or braking unit is being used
Set L8-55 to 0 to disable the braking transistor protection selection.
5.2 Fault Detection
254
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide