beautypg.com

Yaskawa iQpump1000 AC Drive Quick Start User Manual

Page 431

background image

Register No.

Contents

004BH

Drive status (U1-12)
bit 0

During Run

bit 1

During Zero Speed

bit 2

During Reverse Run

bit 3

During Fault Reset Signal Input

bit 4

During Speed Agree

bit 5

Drive Ready

bit 6

Alarm

bit 7

Fault

bit 8

During Operation Error (oPEoo)

bit 9

During Momentary Power Loss

bit A to B

Reserved

bit E

ComRef status, NetRef status

bit F

ComCtrl status, NetCtrl status

004CH to 007EH

Used for various monitors U1-oo, U4-oo, U5-oo and U6-oo.

Refer to U2: Fault Trace on page 404

and

Refer to U3:

Fault History on page 405

for parameter details.

007FH

Alarm Code,

Refer to Alarm Register Contents on page 442

for alarm codes.

0080H to 0097H

Used for monitors U2-oo, U3-oo.

Refer to U: Monitors on page 401

for parameter details and

Refer to Fault Trace

Contents on page 440

for register value descriptions.

0098H

High Word of Accumulated Operation Time Monitor, 10 h units (U4-01)

0099H

Low Word of Accumulated Operation Time Monitor, 1 h units (U4-01)

009AH

High Word of Cooling Fan Operation Time Monitor (U4-03)

009BH

Low Word of Cooling Fan Operation Time Monitor (U4-03)

009CH to 00AAH

Reserved

00ABH

Drive Rated Current

<2>

00ACH to 00AFH

Reserved

00B0H

Option Code Connected to

CN5-A

Register contains ASCII code of the option card.

AO-A3 = 0004H

Communication Option: Register contains ASCII code of first and third digit of the option card

type number.

Example: Register value is 5343H for “SC” if an SI-C3 option card is installed.

00B1H

Reserved

00B2H

Option Code Connected to CN5-B

00B3H

Option Code Connected to CN5-C

00B4H

Reserved

00B5H

Frequency Reference After

Soft-starter (U1-16)

r/min units

<4>

00B6H

0.01% units

00B7H

Frequency Reference

r/min

<4>

00B8H

0.01% units

00B9H to 00BEH

Reserved

00BFH

Lists the last two digits of operation error code oPEoo.

C.9 MEMOBUS/Modbus Data Table

YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide

431

C

MEMOBUS/Modbus Communications