Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 431

Register No.
Contents
004BH
Drive status (U1-12)
bit 0
During Run
bit 1
During Zero Speed
bit 2
During Reverse Run
bit 3
During Fault Reset Signal Input
bit 4
During Speed Agree
bit 5
Drive Ready
bit 6
Alarm
bit 7
Fault
bit 8
During Operation Error (oPEoo)
bit 9
During Momentary Power Loss
bit A to B
Reserved
bit E
ComRef status, NetRef status
bit F
ComCtrl status, NetCtrl status
004CH to 007EH
Used for various monitors U1-oo, U4-oo, U5-oo and U6-oo.
Refer to U2: Fault Trace on page 404
and
007FH
Alarm Code,
Refer to Alarm Register Contents on page 442
0080H to 0097H
Used for monitors U2-oo, U3-oo.
Refer to U: Monitors on page 401
for register value descriptions.
0098H
High Word of Accumulated Operation Time Monitor, 10 h units (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor, 1 h units (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
<2>
00ACH to 00AFH
Reserved
00B0H
Option Code Connected to
CN5-A
Register contains ASCII code of the option card.
AO-A3 = 0004H
Communication Option: Register contains ASCII code of first and third digit of the option card
type number.
Example: Register value is 5343H for “SC” if an SI-C3 option card is installed.
00B1H
Reserved
00B2H
Option Code Connected to CN5-B
00B3H
Option Code Connected to CN5-C
00B4H
Reserved
00B5H
Frequency Reference After
Soft-starter (U1-16)
r/min units
<4>
00B6H
0.01% units
00B7H
Frequency Reference
r/min
<4>
00B8H
0.01% units
00B9H to 00BEH
Reserved
00BFH
Lists the last two digits of operation error code oPEoo.
C.9 MEMOBUS/Modbus Data Table
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
431
C
MEMOBUS/Modbus Communications