Changing parameter settings or values, 3 using the hoa keypad, Press to enter the parameter menu tree – Yaskawa iQpump1000 AC Drive Quick Start User Manual
Page 167: Press or to select the c parameter group, Press two times, Press or to select parameter c1-02, Press, Press to confirm the change
u
Changing Parameter Settings or Values
This example explains changing C1-02 (Deceleration Time 1) from 10.0 seconds (default) to 20.0 seconds.
Note:
During serial communication writing, if a parameter change is also attempted via the HOA keypad, a “BUSY - WRITE PROTECTED”
message will display. Parameter change will not be possible from the HOA keypad until an Enter command is received via the serial
communication to finish the serial writing process.
Step
Display/Result
1. Turn on the power to the drive. The initial display appears.
- MODE -
U5-99= 0.0PSI
U1-02= 0.00Hz
U1-91= 0.0PSI
DRV
Auto Setpoint
Rdy
<-MONITOR->
LSEQ
LREF
2. Press
or
until the Parameter Setting Mode screen appears.
Home
- MODE -
PRG
Programming
FWD
3. Press
to enter the parameter menu tree.
-PRMSET-
Initialization
Select Language
PRG
FWD
A
1-00= 0
Home
DATA
4. Press
or
to select the C parameter group.
-PRMSET-
Basic Setup
Accel Time 1
PRG
FWD
C
1-01=
20.0 sec
FWD
Home
DATA
5. Press
two times.
-PRMSET-
Accel/Decel
Accel Time 1
PRG
FWD
C
1
-01=
20.0 sec
-PRMSET-
C1-
01
= 20.0Sec
(0.0~6000.0)
“20.0 sec”
PRG
Accel Time 1
FWD
Home
Home
DATA
DATA
6. Press
or
to select parameter C1-02.
-PRMSET-
C1-
02
= 10.0Sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
FWD
Home
DATA
7. Press
to view the current setting value (10.0 s). The leftmost digit flashes.
-PRMSET-
C1-02=
0
010.0Sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
Home
FWD
8. Press
F2
or
until the desired number is selected. “1” flashes.
-PRMSET-
C1-02=00
1
0.0Sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
Home
FWD
9. Press
and enter 0020.0.
-PRMSET-
C1-02=00
2
0.0sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
Home
FWD
10. Press
to confirm the change.
Entry Accepted
11. The display automatically returns to the screen shown in Step 6.
-PRMSET-
C1-
02
= 10.0Sec
(0.0~6000.0)
“10.0 sec”
PRG
Decel Time 1
FWD
Home
DATA
4.3 Using the HOA Keypad
YASKAWA TOEP YAIP1W 01B YASKAWA AC Drive - iQpump1000 Quick Start Guide
167
4
Start-Up Programming & Operation