Troubleshooting

ATCA-7350 Installation and Use (6806800G59G)

178

A.9

Power Exceptions

A.9.1

ATCA-7350 Cannot Be Started

Description

The ATCA-7350 cannot be started.

Solution

To solve the problem, proceed as follows:

1. Make sure that the shelf is powered on properly.

For details, refer to the respective system documentation.

2. If you install an optional component on the ATCA-7350, remove the optional component

and then restart the ATCA-7350.

3. Start another ATCA-7350 in the shelf. If it can be started normally, replace the faulty ATCA-

7350.

4. If the problem persists, see

Uncertain Exceptions

on page 183

.

A.9.2

ATCA-7350 Automatically Shuts Down

Description

The ATCA-7350 automatically shuts down without any explicit reason.

Solution

To solve the problem, proceed as follows:

1. Make sure that each component of the shelf is installed properly. For details, refer to the

respective system documentation. If some components are not installed or are installed
improperly, the ATCA-7350 may automatically shut down.

2. Replace the ATCA-7350.