To edit the Event Step table, each of these commands must be issued once to initialize the

parameters; this will take four scans. Once the beginning step number, the ending step

number, and the parameter to be changed have been defined, all the steps can be changed

in a single scan by sending

0XE3

command with the new parameter value. All four of

these commands must be sent on the same axis.

Example:

If you have a step table that is 100 steps long and you want to change the time delay link

value in each step, it would take 100 scans by using the

Event Step Transfer

commands.

If the scan time is 20ms, this would take 2 seconds. By using the Event Step Edit

commands, it would take 80ms for the first change (four scans times 20ms/scan) and only

20ms for another change.
Assuming that the steps we want to modify are step 0 to 99 and the new link value will be

500, the following commands would be sent:
First scan:

4TTTTT+1 0XE0h (Set Start Step Number)

4TTTTT+2

0 (Start Step Number of 0)

Second scan:

4TTTTT+1 0XE1h (Set End Step Number)

4TTTTT+2

99 (End Step Number of 99)

Third scan:

4TTTTT+1 0XE2h (Set Parameter to Modify)

4TTTTT+2

7 (Select LINK VALUE)

Fourth scan:

4TTTTT+1 0XE3h (Set Actual Value)

4TTTTT+2

500 (LINK VALUE itself)

LINK TYPE/NEXT

In order to fit a single Event Step into eight words, the

Link Type

and

Link Next

fields

share a single word. In the most significant byte, the

Link Next

field is stored; in the

least significant byte, the

Link Type

is stored:

Link Next

Link Type

Diagnostics Command

Format: 0000 XXXX 1111 XXXX

X Don’t care.

These commands are for testing the motion controller under safe conditions. This

command echoes the

Output registers

for the axis into the

Input registers

. This tests the

motion controller to Programmable Controller communications.