Plot Time

The plot time field controls the time interval between plot samples. Because the number

of samples for a full graph is fixed, the total graph length is also set by this parameter. In

a full graph, there are 1024 samples. The plot time units are 1000/1024 milliseconds.

Therefore, to request the graphs on an axis to be 4 seconds in length, this parameter

should be set to 4. This will result in 1024 samples, each 4000/1024 milliseconds apart,

for a total length of 4000 milliseconds.
The following two equations can be used for requesting a plot length:

Full Plot Length = PLOT TIME x 1 second
Plot Interval =

PLOT TIME x 1000 ms

1024

Special Status Values Available in Plots

TARGET SPEED
The target speed is displayed in a plot, both graphically and in the detail window, but it is

not displayed in the main status area. Like the

ACTUAL SPEED

, this parameter is

calculated. However, instead of being calculated off of

TRANSDUCER COUNTS

, it is

calculated from the

TARGET POSITION

. Therefore, when viewing a plot you can

compare the

ACTUAL

and TARGET SPEEDS to determine how well the actual move is

tracking the intended move.

Why is the TARGET SPEED Jagged During Constant Velocity?

With older versions of the firmware and monitor software, you may notice that during

some constant velocity moves, the TARGET SPEED is not flat. The jaggedness caused

by quantizing. That is, suppose that at constant velocity the axis is moving an average of

4.8 position units per millisecond. Because the motion controller only reads whole

numbers of position units, the

TARGET POSITION

would appear to increase by 4

position units for four milliseconds, and every fifth millisecond it would move 5 position

units. Therefore, if we were to calculate the speed based on a single interval, the speed

would just by 25% every fifth interval.
When the TARGET SPEED is calculated, smoothing is performed so that the speed does

not vary by 25%, but some jaggedness is left from rounded-off position units.

Raw Transducer Counts
The MDT Counts (lo) field holds bits 0-15 bits of the

TRANSDUCER COUNTS

at the

given plot time period. The MDT Counts (hi) field is provided for use by technical