both the '+Int' and '-Int' between the transducer and the MMC120 for the interrogate

signal, and connect both the '+Ret' and '-Ret' between the transducer and the MMC120

for the return signal. Connect the transducer DC ground to MDT Common.

For single-ended transducer with positive interrogation, connect the transducer '-

interrogation in' wire to the ‘MDT Cmn’ pin and the transducer '+ interrogation in' wire

to the '+ Int' pin. CONNECT NOTHING TO THE '-Int' PIN OF THE MMC120.

Connect the transducer return plus wire to the '+Ret’ pin on the MMC120 and the

transducer return common wire to ‘MDT Cmn’ on the MMC120. CONNECT

NOTHING TO THE '-Ret' PIN OF THE MMC120.

Temposonics I transducer users:

For the negative interrogation version of this transducer, connect the transducer '+

interrogation in' wire to the ‘MDT Cmn’ pin and the transducer '- interrogation in' wire to

the '-Int' pin. CONNECT NOTHING TO THE '+Int' PIN OF THE MMC120. Connect

the transducer return plus wire to the '+Ret’ pin on the MMC120 and the transducer

return common wire to ‘MDT Cmn’ on the MMC120. CONNECT NOTHING TO THE

'-Ret' PIN OF THE MMC120.