Some Temposonics I transducers from MTS have 200 Ohm termination resistors installed

between their interrogation pins and common. If yours do not, it may be necessary to

install them as close to the transducers as possible to reduce electrical noise in the system.

Serial Port

DB-9

Pin

Function

2

Receive

3

Transmit

5

Common

The communication cable attached to the serial port is a potential source of

electromagnetic radiation from the MMC120. To minimize radiation, use a well-shielded

cable that is as short as possible, and route it out the bottom of the module and against the

back panel.
A standard Modicon Modbus cable will work in this port, or one can be built using the

following diagram: