Click here for MDT SCALE Calculation examples

NOTE: When the SCALE parameter is changed, the

EXTEND LIMIT

,

RETRACT

LIMIT

, and

OFFSET

must also be changed.

NOTE:You should never set the SCALE below 16383. If it does go below that value,

then use the Prescale Divisor bits in the

CONFIGURATION WORD

. As you

can see from the

ACTUAL POSITION

calculation above, this will affect the

scaling, but will reduce round-off errors.

SCALE Calculation Examples

Example 1

For a system using a magnetostrictive transducer with a calibration number of

9.1392

µ

s per inch, a position unit of 0.001 inch, and 1 recirculation, the

SCALE

will be:

scale =

1000(

Position Units Per Inch) x 32768= 29878.62

9.1392(

µ

s/in) x 120MHz x 1 (Recirculations)

SCALE = 29879

Example 2

For a system using a magnetostrictive transducer with a calibration number of

9.0110

µ

s per inch, a position unit of 0.1 millimeter, and 1 recirculation, the

SCALE

will be:

scale =

254(Position Units Per Inch) x 32768 = 7697.14

9.0110(

µ

s/in) x 120MHz x 1 (Recirculations)

Since the scale is less than 16383.5, use the Prescale Divisor bits in the

CONFIGURATION WORD

to divide the transducer counts by 4. Then multiply

the scale by 4 to obtain:

SCALE = 7697.14 x 4 = 30789

Example 3

For a system using a magnetostrictive transducer with a calibration number of

8.9772

µ

s per inch, a position unit of 0.001 inch, and 8 recirculations, the

SCALE

will be:

scale =

1000(Position Units Per Inch) x 32768 = 3802.22

8.9772(

µ

s/in) x 120MHz x 8 (Recirculations)