Null drive, Step, Link value – Delta MMC120 User Manual
Page 130
130
NULL DRIVE
This field displays the amount of drive in millivolts that it takes to hold the
ACTUAL
POSITION
at the
TARGET POSITION
while at rest. Ideally this number should be zero
if the valve is perfectly nulled. This field is automatically updated toward the Integral
Drive when the
ACTUAL POSITION
is exactly equal to the
COMMAND POSITION
and the speed is zero.
This field is only used in open loop mode. NULL DRIVE gets added to the drive output.
Why Bother?
The NULL DRIVE field can be used to null valves and drives. Usually there is a null or
offset adjustment on the valve or amplifier that can be adjusted so the NULL DRIVE is 0.
STEP
This field shows the current step the axis is executing of the 256 steps in the Event Step
Table. This is valid only when Event Control is being used. Use this field in conjunction
with the
Link Value
status word to monitor the progress of an axis through the step table.
LINK VALUE
This field is used only when the axis is using the Event Step Table. It represents the
current event step
link value
of the current step for the axis. The current step is displayed
in the
STEP
status word.
For delay link types (types ‘D’ and ‘d’), this field displays the number of delay units left
(in either counter ticks or milliseconds).
Appendix E: Event Step Link Reference
Link Types and Link Values
Link Type and Link Value specify the condition that causes the motion controller to
execute the
next step
in a sequence. These fields may be edited manually; however in
most cases it is easier to use the Popup Editor. Start the popup editor by pressing Enter
in, or double-clicking on, either the Link Type or Link Value field.
The Link Type and Link Value dialog box divides the link types into three categories:
•
System-wide (Basic, non-axis dependent)
These link types allow the axis to wait on a global condition such as a time delay.
These link types are listed below; select a link type for further details: