Why use the Motion Profile Table?
The PLC can issue only a
Command
and
Command Value
in a single command cycle.
Therefore, the
Go
command can only give the Requested Position as the command value,
so to set the entire motion profile and give the
Go
command would require five
commands. While this is flexible, it requires a great deal of programming and run-time.
By using the Motion Profile Table, a complete move including all four motion profile
fields can be set with a single
Go Using Profile
command, speeding up both execution
and development time.
How is the Motion Profile Table Used?
The
Go Using Profile
and
Open Loop Using Profile
commands select one of the 16
motion profiles in the table and use that profile to issue the command.
How is the Motion Profile Table Changed?
There are two ways to the change the motion profiles table:
•
Use the Motion Profile Table Editor. On the Tools menu, click Profile Editor to start
this editor; see
Editing the Profile Table
for details.
•
Use the
Set Profile
commands to change the table from the PLC.
How do I Save the Motion Profile Table?
There are three places where the Motion Profile Table can be saved:
•
FLASH
memory. Use the
Update FLASH
command to store the current profile table
in the FLASH memory.
•
Disk file. The table can be saved to disk from within the
Motion Profile Table Editor
.
•
PLC memory. Use the
Set Profile
and
Get Profile
commands to send the table to and
from the PLC.
What are the Default Motion Profile Values?
When the motion controller starts, it first does a checksum on the profile table in the
FLASH
memory. If the FLASH-stored profile table checksum is correct, it is used. If
the checksum is incorrect, then the following default profiles are used:
Profile
0
1
2
3
MODE
0
0
0
0
ACCEL
1000
2000
5000
8000
DECEL
1000
2000
5000
8000
SPEED
1000
2000
5000
8000
Profile
4
5
6
7
MODE
0
0
0
0