Delta MMC120 User Manual
Page 62
62
registers
and 4TTTTT represents the base address for the
output registers
. These are the
addresses at which the MMC120 is configured.
Memory Requirements
The MMC120 has non-volatile
FLASH memory
that can be used for parameter,
profile
and
event step
storage. If you also want to store the parameters in the Programmable
Controller’s memory you must reserve 32 words (registers) of memory—16 per axis.
Tip: Use the monitor program to set up and modify the parameters, profiles and event
steps. Then move them to the programmable controller.
This memory contains the initialization parameters for the axis. The parameters are
arranged in the following order:
0
CONFIGURATION Word
1
SCALE
2
OFFSET
3
EXTEND LIMIT
4
RETRACT LIMIT
5
PROPORTIONAL GAIN
6
INTEGRAL GAIN
7
DIFFERENTIAL GAIN
8
EXTEND FEED FORWARD
9
RETRACT FEED FORWARD
10
EXTEND ACCELERATION FEED FORWARD
11
RETRACT ACCELERATION FEED FORWARD
12
DEAD BAND ELIMINATOR
13
IN POSITION
14
FOLLOWING ERROR
15
AUTO STOP
In addition to the parameter storage blocks, memory may be allocated for
profile
and
event step
storage if these features are used.
Each
profile
requires four words of memory, and each module can use up to 16
profiles
.
The first eight
profiles
can be changed from the PLC and all 16 can be changed from the
monitor program. Only enough memory must be allocated to hold the
profiles
used in all
the modules in the system. The
profiles
consist of Mode, Acceleration, Deceleration and
Speed information.
If you use
Event Control
and want to store the step sequences on the PLC, you must
reserve eight registers for each step used.
The demo program on the monitor program disk shows an example of ladder logic for
transferring parameters,
profiles
and
Event Control steps
to and from the MMC120.