beautypg.com

Led indicators – Delta MMC120 User Manual

Page 54

background image

54

The entire step table

Each section is protected by a checksum; these checksums are tested on module power-

up and reset.

Determining if the FLASH Data was Used

Prior to issuing the first

Set Parameters

command on an axis, the Initialized bit in the

STATUS

word will be cleared. While this bit is cleared, the Parameter error bit in the

STATUS

word of each axis will indicate whether the FLASH memory checksums were

valid.
If the parameter error bit for axis 1 is set on startup, then the checksum for section 1 was

invalid and default parameters and profiles will be used. If the parameter error bit for

axis 2 is set on startup, then the checksum for section 2 was invalid and a blank step table

will be used.

Storing Data in the FLASH

To update the FLASH information, you must first download correct data to the MMC120

volatile memory. Use the

Set Parameter

,

Set Profile

, and

Event Step Transfer

commands

to download the information to the motion controller.
After the data to be stored has been downloaded to the motion controller’s volatile

memory, transfer it to the FLASH memory using the

Update FLASH

command. To

transfer data to section 1 (both parameters and profiles), put a ‘1’ in the

COMMAND

VALUE

field when the

Update FLASH

command is issued. To transfer data to section 2

(event steps), put a ‘2’ in the

COMMAND VALUE

field when the

Update FLASH

command is issued.
The Acknowledge bit of the

STATUS

word is used to report the result of the update. If

the FLASH updated successfully, then the Acknowledge bit of axis 1 is toggled.

Otherwise the Acknowledge bit of axis 2 is toggled.
The disadvantage of storing configuration data in the motion controller is that, when one

module is replaced with another, the parameters, profiles and event steps must be loaded

into the new module. Because of this, all parameters, profiles and event step table data

must be stored either in the control program or in monitor program files so they can be

later transferred to the motion controller when needed.

LED Indicators

There are 14 green and red light emitting diodes (LEDS) used on the front panel of the

MMC120. These LEDS provide status information about the module and each of the two

axes.
The LED labeled “F” is the FAIL indicator for the MMC120 microprocessor. If the

FAIL indicator is red, the drive outputs are disabled, and the axes will not move unless

the value is out of null.
The LED labeled “Active” indicates the status of communications over the back plane.

When this LED is green, communication is normal. When it is off, the communication