Model 5700 installation and operation manual – SilentKnight 5700 User Manual
Page 96

Model 5700 Installation and Operation Manual
151295
6-23
System
Options
(cont.)
System Event
Outputs
Trouble Events
System Trouble
Select Group
None selected
Section 7.6.3.1
Select Cadence
Alarm Silence
Select Group
None selected
Select Cadence
Trbl Silence
Select Group
None selected
Select Cadence
User Selected
Group Tr
Select Group
(*None)
Select Cadence
(*None)
SBUS Com
SBUS Pwr
SLC Loop
AC Loss
Battery
Gnd Flt
Phone Ln
Account
Printer
Aux Pwr
Sys Sw
Sys Alarm Cadence
Fire Drill Cadence
00-21, 23
*00 (Constant)
Section 7.6.3.2
System Aux1
Cadence
00-21, 23
*00 (Constant)
System Aux2
Cadence
00-21, 23
*00 (Constant)
Time Options
Water Flow Delay
0 - 90 Seconds
*01 sec
Water Flow delay is the number of sec.
before water flow alarm is generated.
Section 7.6.6.1
Alarm Verification
time
Enter time from 1 to
250 seconds
*60 Seconds
Section 7.6.6.2
Low AC Delay
0 - 30 hours
*3 hrs
Low AC Report Delay. Section 7.6.6.3
Clock
AM/PM
*AM/PM
System Clock Format (AM/PM or
military). Section 7.6.6.4
MIL
AC Freq:
50 Hz
Section 7.6.6.5
60 Hz
Neither
Misc. Options
SYNC Strbs w/ Sil
Y (Enabled)
*Disabled
N (Disabled)
Auto Display Oldest
Y (Enabled)
*Enabled
Section 7.6.7.2
N (Disabled)
Report By
Zone
*Zone
Section 7.6.7.3
Point
Single Key Ack
Y (Enabled)
*Disabled
N (Disabled)
Menu
Options/Defaults
Comments