beautypg.com

Model 5700 installation and operation manual – SilentKnight 5700 User Manual

Page 96

background image

Model 5700 Installation and Operation Manual

151295

6-23

System
Options

(cont.)

System Event
Outputs

Trouble Events

System Trouble

Select Group

None selected

Section 7.6.3.1

Select Cadence

Alarm Silence

Select Group

None selected

Select Cadence

Trbl Silence

Select Group

None selected

Select Cadence

User Selected

Group Tr

Select Group
(*None)

Select Cadence
(*None)

SBUS Com

SBUS Pwr

SLC Loop

AC Loss

Battery

Gnd Flt

Phone Ln

Account

Printer

Aux Pwr

Sys Sw

Sys Alarm Cadence

Fire Drill Cadence

00-21, 23

*00 (Constant)

Section 7.6.3.2

System Aux1
Cadence

00-21, 23

*00 (Constant)

System Aux2
Cadence

00-21, 23

*00 (Constant)

Time Options

Water Flow Delay

0 - 90 Seconds

*01 sec

Water Flow delay is the number of sec.
before water flow alarm is generated.
Section 7.6.6.1

Alarm Verification
time

Enter time from 1 to
250 seconds

*60 Seconds

Section 7.6.6.2

Low AC Delay

0 - 30 hours

*3 hrs

Low AC Report Delay. Section 7.6.6.3

Clock

AM/PM

*AM/PM

System Clock Format (AM/PM or
military). Section 7.6.6.4

MIL

AC Freq:

50 Hz

Section 7.6.6.5

60 Hz

Neither

Misc. Options

SYNC Strbs w/ Sil

Y (Enabled)

*Disabled

Section 7.6.7.1

N (Disabled)

Auto Display Oldest

Y (Enabled)

*Enabled

Section 7.6.7.2

N (Disabled)

Report By

Zone

*Zone

Section 7.6.7.3

Point

Single Key Ack

Y (Enabled)

*Disabled

Section 7.6.7.4

N (Disabled)

Menu

Options/Defaults

Comments