5 zone accessory options, 2 add zone, 3 delete zone – SilentKnight 5700 User Manual
Page 107: 4 view zone points, 5 zone accessory options -9, N 7.3.1.5, N 7.3.2, Ection 7.3.3

Model 5700 Installation and Operation Manual
151295
7-9
7.3.1.5 Zone Accessory Options
This option applies to detectors that are used with Sounder bases and Relay bases.
Fire Cadence:_ _ / CO Cadence:_ _ (choose from a subset of Patterns 00 to 23).
Note: The B200S Sounder bases is intended to be used along with the CO Cadence setting. Local Zone (choose
Y (Yes) or N (No).
7.3.2
Add Zone
To add a zone, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 2 to enter zone menu.
4.
Press 2 to add a zone.
A zone will be added. The system will assign the next available zone number. Options for this zone can now
be programmed through the Zone Edit sub-menu. Up to 125 zones can be used.
7.3.3
Delete Zone
To delete a zone, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 2 to enter zone menu.
4.
Press 3 to delete a zone.
5.
Select a zone to delete.
A warning screen will display. If you want to proceed with deleting the zone, select Yes. To cancel, select
No.
7.3.4
View Zone Points
To view the points in a zone, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Press 2 to enter zone menu.
4.
Press 4 to view zone points.