1 water flow delay, 2 alarm verification time, 3 low ac report delay – SilentKnight 5700 User Manual
Page 126: 4 clock display format (am/pm or military), N 7.6.6.1, N 7.6.6.3, Tion 7.6.6.4

Programming
151295
7-28
7.6.4.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 5 for Time Options.
A screen similar to the one shown in Figure 7-21 will display.
Figure 7-18 Water Flow Delay Programming Screen
5.
Enter the number of seconds (0 to 90) to delay an a water flow switch alarm, then press
ENTER
.
7.6.4.2 Alarm Verification Time
You can set the alarm verification time from 1 to 250 seconds (default is 60 seconds).
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press
or ENTER
to make your selection and move to the next programming option.
7.6.4.3 Low AC Report Delay
Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a Low AC report will be sent to the central station.
To program low AC report delay, follow these steps:
Note: Steps continued from step 7 of Section 7.6.6.2.
Figure 7-19 Low AC Report Delay Programming Screen
8.
Enter the number of hours before a low AC report will be sent to the central station, then press
ENTER
. Refer
7.6.4.4 Clock Display Format (AM/PM or Military)
To change the system clock display format, continue programming from step 8 above:
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
Low AC Report
Delay in Hours
(00 - 30)