beautypg.com

5 change ac line frequency, 5 miscellaneous options, 1 synchronize strobes active during silence – SilentKnight 5700 User Manual

Page 127: 2 auto display oldest event, 3 report by zone or by point, 5 change ac line frequency -29, 5 miscellaneous options -29, N 7.6.6.5, Ection 7.6.7.1

background image

Model 5700 Installation and Operation Manual

151295

7-29

9.

Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the

or

arrow, then press

ENTER

.

7.6.4.5 Change AC Line Frequency

The panel’s AC line frequency is selectable for 60 Hz or Neither. AC Frequency feature dictates how the control
panel will calculate time based on the AC line frequency used in the installation site. The “Neither” option can be
used in areas where the AC line frequency is not dependable and you want the panel to calculate time from the
internal crystal. The internal crystal is not as accurate as the AC power source and 60 Hz should normally be
selected. The panel defaults to the 60 Hz. selection.

To change the AC line frequency, continue programming from step 9 above:

10. Select 60 or Neither, by pressing the

or

arrow, then press

ENTER

.

7.6.5

Miscellaneous Options

Through this programming option you can turn on or off strobe synchronization during silence, display status at
idle (auto display event), report by zone or point, and single key ack.

To edit miscellaneous options:

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Select 5 for System Options.

4.

Select 6 for Miscellaneous Options.

7.6.5.1 Synchronize Strobes Active During Silence

When “SYNC Strbs w/ Sil:” is Selected as Y (Yes) then strobes will continue to flash when the system is silenced
and will stop flashing when the system is reset.

Note: The “SYNC Strbs w/ Sil:” only functions with outputs that use a synchronized output pattern.

5.

Press the

or

arrow to toggle this selection between Y (Yes) or N (No).

6.

Press

or ENTER

to make your selection and move to the next programming option.

Note: See Section 7.3.1.4 for more information about Synchronization protocol choices.

7.6.5.2 Auto Display Oldest Event

When this feature is programmed Y (Yes) then the oldest un-acknowledge event will automatically display on
the control panel and remote annunciators after there has been no activity on any system touchpad for two
minutes.

7.

Press the

or

arrow to toggle this selection between Y (Yes) or N (No).

8.

Press

or ENTER

to make your selection and move to the next programming option.

7.6.5.3 Report by Zone or by Point

When the “Report by” option is set to Zone, then the control panel will report events by zone. If Point is selected
then the control panel will report events by point.

9.

Press the

or

arrow to toggle this selection between Zone or Point.