10.3 Built-in Troubleshooting and Testing Tools

The fire control panel has several built-in testing and troubleshooting tools that can be utilized to save time while
testing and troubleshooting points and SLC devices.

10.3.1

SLC Device Locator

SLC device locator can be used to locate a device on a SLC loop.

Follow these steps to locate a particular SLC device:

1.

Select 2 (Point Functions) from the Main Menu.

2.

Select 4 (SLC Dev Locator).

A message similar to the one shown in Figure 10-1 will display.

Figure 10-1 Shut Down Warning

3.

Press the

or

arrow to toggle NO to YES then press

ENTER

.

If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.

4.

Select the SLC loop.

5.

Enter the SLC address of the device you wish to locate.

The LED on the selected device will start flashing.

6.

Press left arrow to exit SLC device locator function.

Note: Once you exit the system will resume normal operation.

10.3.2

SLC Multi Locator

This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a single search.

Follow these instructions to locate multiple SLC devices:

1.

Select 2 (Point Functions) from the Main Menu.

2.

Select 5 (SLC Multi Locator).

A message similar to the one shown in Figure 10-1 will display.

Figure 10-2 Shut Down Warning