Model 5700 Installation and Operation Manual

151295

8-9

8.5

Operation Mode Behavior

The control panel can be in one of seven conditions at any given moment: Normal, Alarm, Prealarm,
Supervisory, Trouble, Silenced, and Reset. Table 8-1 describes the behavior of the panel in each of these modes.

Table 8-1: Operation Modes of FACP

Operation

Mode

Occurs

When

System Behavior

In This Mode You Can

Normal

No alarm,
supervisories
or trouble con-
dition exists
and menus are
not in use.

SYSTEM POWER LED is on.

The All Systems Normal display indicates
that the system is in normal mode.

The current date and time display on the
last line of the LCD.

Enter the appropriate code, or rotate the key
to activate the Main Menu.

Alarm

A smoke
detector goes
into alarm or a
pull station is
activated.

CO detector
goes into
alarm.

If more than 3
categories are
active at a
single time
screen will
display as
shown.

The dialer seizes control of the phone line
and calls the central station.

The on-board annunciator sounds a loud,
steady beep (any notification devices
attached to the system will also sound).

GENERAL ALARM LED flashes.

The LCD displays a screen similar to this
one.

Press the down arrow to view the alarm. A
screen similar to this one displays.

Press SILENCE and enter an access code
(or activate the key) to silence the
annunciator (and any notification devices
attached to the system).

When the alarm condition clears, press
RESET and enter a code (or activate the
key) to restore the panel to normal.

After sitting idle, events will display in a
screen similar to this:

Note: Alarm and Prealarm are

combined into a single
alarm count