6 answering machine bypass, 3 sys. event outputs, 1 trouble events – SilentKnight 5700 User Manual
Page 124: 6 answering machine bypass -26, 3 sys. event outputs -26, 1 trouble events -26, N 7.6.3.1

Programming
151295
7-26
10. Select Y (monitor line) or N (don’t monitor line) by pressing the
or
arrow, then press
ENTER
.
7.6.2.6 Answering Machine Bypass
This option is used in conjunction with the Silent Knight Software Suite 5660. This feature ensures that an
answering machine will not interfere with communication between the panel and the computer. If an answering
machine is used at the panel site, enable this feature; if an answering machine is not used, disable the feature.
This option is factory-programmed as Yes (enabled).
The selection made here must match the programming for this option in the Communication Configuration
dialog box of the 5660 software. See the manual for the software (p/n 151240) if you need more information.
11. Select Y (answering machine bypass enabled) or N (answering machine bypass disabled) by pressing the
or
arrow, then press
ENTER
.
7.6.3
Sys. Event Outputs
1.
Enter the installer code.
2.
Select 7 for Program Menu.
3.
From the Program Menu, select 5 for System Options.
4.
From the System Options Menu, select 2 for Sys. Event Outputs.
7.6.3.1 Trouble Events
You can map certain system trouble events to an output group. To access the screen for selecting output groups
and cadence patterns for system trouble events.
5.
Press 1 for Trouble Events. A screen similar to the one in Figure 7-16 will display. Select a group and a
cadence pattern for each event as needed for your application. The U: field is for a user-specified trouble
condition. You can program an output group and cadence pattern for any of the following events:
Battery
Low battery condition
Phone Ln
Phone Line 1 or 2 trouble
Account
Account trouble; cannot report to account
Printer
Printer trouble
Aux Pwr
Auxiliary power trouble
Sys Sw
Trouble with a system switch
Group Tr
Trouble with an output group
SBUS Com
SBUS communication trouble
SBUS Pwr
SBUS power trouble
SLC Loop
Trouble on the SLC loop
AC Loss
AC power lost