14 view status of a point, 14 view status of a point -6 – SilentKnight 5700 User Manual
Page 138

System Operation
151295
8-6
When a CAL TRBLE condition occurs, the central station receives a detector trouble report (“373” and the zone
or point for Contact ID format; “FT” and the zone or point in SIA format).
To check sensitivity for an individual detector, follow the steps below. Section 8.4.19 provides instructions for
printing the status of all detectors in the system.
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press
ENTER
.
5.
A screen similar to those shown in Figure 8-3 will display.
Figure 8-3 Checking Detector Sensitivity Compliance
If a printer is attached to the system (via a Module 5824 Serial/Parallel Interface), you can print detector status
(see Section 8.4.19).
8.4.14
View Status of a Point
1.
From the Main Menu, select 2 for Point Status.
2.
From the list that displays, press
ENTER
to select the module where this point is located. The screen that dis-
plays will show you if the point has a trouble and will provide sensitivity compliance information. (See Sec-
tion 8.4.13 for complete information about detector sensitivity compliance.)