14 view status of a point, 14 view status of a point -6 – SilentKnight 5700 User Manual

Page 138

background image

System Operation

151295

8-6

When a CAL TRBLE condition occurs, the central station receives a detector trouble report (“373” and the zone
or point for Contact ID format; “FT” and the zone or point in SIA format).

To check sensitivity for an individual detector, follow the steps below. Section 8.4.19 provides instructions for
printing the status of all detectors in the system.

1.

From the Main Menu, press 2 for Point Functions.

2.

Press 2 for Point Status.

3.

Select the module where the point you want to check is located.

4.

Enter the number of the point you want to check and press

ENTER

.

5.

A screen similar to those shown in Figure 8-3 will display.

Figure 8-3 Checking Detector Sensitivity Compliance

If a printer is attached to the system (via a Module 5824 Serial/Parallel Interface), you can print detector status
(see Section 8.4.19).

8.4.14

View Status of a Point

1.

From the Main Menu, select 2 for Point Status.

2.

From the list that displays, press

ENTER

to select the module where this point is located. The screen that dis-

plays will show you if the point has a trouble and will provide sensitivity compliance information. (See Sec-
tion 8.4.13 for complete information about detector sensitivity compliance.)