Programming Overview
151295
6-12
6.5
Programming Menu Quick Reference
This section of the manual lists all Program Menu options in the order they appear on the sub-menus. Default
settings are indicated in text or marked with an asterisk. The comments column provide quick information and a
reference to a section (if applicable) which has more detailed information.
Menu
Options/Defaults
Comments
Module
Edit Module
Select Module
Enter Module ID
Enter Module
Name
Edit Module
Settings (if
applicable)
Section 7.2.1
Add Module
5824-Ser/Par/IO
Section 7.2.2
5860-LCD Ann
5895XL Pwr Sup
5496-NAC Expand
5880-LED/IO Dev
5865-LED Annunc
Delete Module
List of Modules
View Module List
List of Modules
Section 7.2.4
Zone
Edit Zone
Select Zone to Edit
Edit Zone Name
Zone Properties
Verification Type
*1 Count
Section 7.3.1.2
2 Count
Alarm Ver.
PAS
SNGL ILOCK
DBL ILOCK
Heat Temp Set
135° to 150°F*
SD Devices.
Section 7.3.1.2
135° to 190°F,
*150°F
SK Devices.
Section 7.3.1.2
Zone Outputs
Manual Pull (MP)
*Groups 01, 125;
Pattern 00
Section 7.3.1.3
Section 7.3.1.4
Water Flow (WF)
Detector Alarm
(DE)
Aux 1 (A1)
*No Groups
Aux 2 (A2)
Pre-alarm (PR)
Fire Supervisory
(SU)
Group 124; Pattern
00
Trouble (TR)
*No Groups
Status Point (SP)
CO Alarm (CO)
*Groups 01, 125;
Pattern 00
CO Supervisory
(Sco)
*Group 124;
Pattern 00