The below table lists two-wire smoke detectors that are compatible with the fire control panel. The
table is organized by manufacturer. The columns show the number of detectors per loop that can be
used.
Note: The maximum number of smoke detectors per zone is determined by both the current draw and
the impedance of the smoke detector. If too many smoke detectors are used on any zone, false
alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed
in that configuration.
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the
maximum reset time of the smoke detector.
5700
Identifier
24H
Operating Voltage Range
18.5–27.4 VDC
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer
Model Name or Number
(Base model name or number
in parentheses.)
Compatibility ID
# per Loop
Head
Base
Apollo
55000-350 (45681-200)
55000-350
45681-200
24 / loop
55000-250 (45681-200)
55000-250
45681-200
24 / loop
ESL
429C (S10A)
N/A
S10A
30 / loop
429CRT (S11A)
N/A
S11A
30 / loop
429CST (S11A)
N/A
S11A
30 / loop
429CT (S10A)
N/A
S10A
30 / loop
609U01-11
S10
S00
40 / loop
609U02-11
S10
S00/S03
40 / loop
611U (601U or 602U)
S10
S00/S03
40 / loop
611UD (601U or 602U)
S10
S00/S03
40 / loop
611UT (601U or 602U)
S10
S00/S03
40 / loop
612U (601U or 602U)
S10
S00/S03
40 / loop
612UD (601U or 602U)
S10
S00/S03
40 / loop
711U (701E or 701U)
N/A
S10A
25 / loop
712U (701E or 701U)
N/A
S10A
25 / loop
713-5U (702E or 701U)
N/A
S10A
25 / loop
713-6U (702E or 701U)
N/A
S10A
25 / loop
721-U (S10A)
N/A
S10A
30 / loop
721-UT (S10A)
N/A
S10A
30 / loop