Point

You may need to change characteristics of individual input points (detectors and switches) even after using
JumpStart. This section explains how to change options for: type of point, latching/non-latching, silenceable/
non-silenceable, zone assignment (input points), detector accessory base options, group assignment (output
points), and point name.

7.5.1

Point Programming For SLC

To program for points, follow these steps:

1.

Enter the installer code.

2.

Select 7 for Program Menu.

3.

Press 4 to enter point menu.

4.

Press the

or

arrows to select the desired module. refer to Section 6.5 Quick Reference Table for avail-

able choices.

5.

Enter the number of the point you wish to edit, then press

ENTER

.

6.

Select the type of device by pressing the

or

arrows. Refer to Table 7-5 under the column heading

“Type Selection” for a list of choices.

Table 7-4: Point Programming

Module Type

Type

Selection

Function

Latching

Option

Comments

SLC Loop

UNUSED

SD
DETECTOR

PHOTO

ION

HEAT

PHOT DUCT

ION DUCT

2WIRE SMK

SD SUP
DET

SUP PHOTO

Latching

Non Latching

SUP ION

SUP HEAT

SK
DETECTOR

PHOTO

ION

HEAT

PHOT DUCT

ION DUCT

2WIRE SMK

ACCLIMATE

HEAT HT

PHOTO-HEAT

BEAM