Model 5700 Installation and Operation Manual

151295

2-3

applications, and hotel/motel room applications.

The system allows the Alarm Verification time to be set from 1 to 255 seconds. For UL certified installations
the setting must be a maximum of 60 seconds.

Call forwarding shall not be used.

When two count is used detector spacing shall be cut in half, you shall not use the alarm verification feature,
and no delay shall be used.

P.A.S (positive alarm sequence) feature shall be used only with automatic detectors.

2.2.2

Requirements for Central Station Fire Alarm Systems

1.

Use both phone lines. Enable phone line monitors for both lines.

2.

You must program a phone number and a test time so that the 5700 sends an automatic daily test to the cen-
tral station.

3.

The AC Loss Hours option must be set from 6-12 hours.

4.

The Attempts to Report option must be set for 5.

2.2.3

Requirements for Local Protected Fire Alarm Systems

At least one UL listed supervised notification appliance must be used.

2.2.4

Requirements for Remote Station Protected Fire Alarm
Systems

1.

Do not exceed the current load restrictions shown in Section 3.6.

2.

The AC Loss Hours option must be set from 1-3 hours.