SilentKnight 5700 User Manual

Page 114

background image

Programming

151295

7-16

SLC Loop

SK SUP
DETECTOR

SUP PHOTO
DUCT

Latching

Non Latching

Supervisory switches can be latching or non-
latching.

SUP SMOKE
PHOTO

SUP SMOKE
ION

SUP HEAT

SUP
ACCLIMATE

SUP HEAT HT

SUP SMOKE
PHOTO/HEAT

SUP SMOKE
BEAM

CO SMOKE
DETECTOR

ALRM CO/
ALRM FIRE

SUP CO/ALRM
FIRE

ALRM CO/SUP
FIRE

SUP CO/SUP
FIRE

Latching

Non Latching

Supervisory can be latching or non-latching.

SWITCH

MAN_PULL

Use this switch type for manual pull stations. This
input is always latched. The switch can clear only
when an alarm is reset.

WATERFLOW

Latching

Non Latching

Use this switch type for monitoring water flow in a
sprinkler system. Switch closure will cause a
sprinkler alarm. Water flow switches can be
programmed as latching or non-latching.

You can program a delay of up to 90 seconds to be
used with a water flow switch. The delay allows for
normal, brief changes in sprinkler system water
pressure. The water flow alarm will not activate
unless the switch is active for the programmed
delay time.

Note:

Waterflow delay of the FACP and the wa-

terflow device shall not exceed 90 seconds.

If a delay is used, the system begins counting
down when the switch closes. If the switch opens
(restores) before the timer expires, a water flow
alarm is not generated. If the water flow switch
remains closed after the timer expires, a water flow
alarm will be generated.

Table 7-4: Point Programming

Module Type

Type

Selection

Function

Latching

Option

Comments