SilentKnight 5700 User Manual
Page 114

Programming
151295
7-16
SLC Loop
SK SUP
DETECTOR
SUP PHOTO
DUCT
Latching
Non Latching
Supervisory switches can be latching or non-
latching.
SUP SMOKE
PHOTO
SUP SMOKE
ION
SUP HEAT
SUP
ACCLIMATE
SUP HEAT HT
SUP SMOKE
PHOTO/HEAT
SUP SMOKE
BEAM
CO SMOKE
DETECTOR
ALRM CO/
ALRM FIRE
SUP CO/ALRM
FIRE
ALRM CO/SUP
FIRE
SUP CO/SUP
FIRE
Latching
Non Latching
Supervisory can be latching or non-latching.
SWITCH
MAN_PULL
Use this switch type for manual pull stations. This
input is always latched. The switch can clear only
when an alarm is reset.
WATERFLOW
Latching
Non Latching
Use this switch type for monitoring water flow in a
sprinkler system. Switch closure will cause a
sprinkler alarm. Water flow switches can be
programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be
used with a water flow switch. The delay allows for
normal, brief changes in sprinkler system water
pressure. The water flow alarm will not activate
unless the switch is active for the programmed
delay time.
Note:
Waterflow delay of the FACP and the wa-
terflow device shall not exceed 90 seconds.
If a delay is used, the system begins counting
down when the switch closes. If the switch opens
(restores) before the timer expires, a water flow
alarm is not generated. If the water flow switch
remains closed after the timer expires, a water flow
alarm will be generated.
Table 7-4: Point Programming
Module Type
Type
Selection
Function
Latching
Option
Comments