beautypg.com

Model 5700 installation and operation manual – SilentKnight 5700 User Manual

Page 26

background image

Model 5700 Installation and Operation Manual

151295

3-9

SD500-ANM

(50 max.)

1

Aux. Pwr

Standby: 8 mA

mA

Alarm: 60 mA

mA

SLC

Standby/Alarm: .55 mA

mA

mA

SD500-LED

(50 max.)

1

Aux. Pwr

Standby: 10 mA

mA

Alarm: 220 mA

mA

LED: 10 mA

mA

mA

SLC

Standby/Alarm: .55 mA

mA

mA

SD500-SDM

(50 max.)

1

Aux. Pwr

Standby: 20 mA

mA

Alarm: 106 mA

mA

SLC

Standby/Alarm: .55 mA

mA

mA

SLC Accessory Bases

SD505-6RB

(50 max.)

Standby/Alarm: .082 mA

mA

mA

SD505-6SB

(50 max.)

Aux. Pwr

Standby: 1 mA

mA

Alarm: 32 mA

mA

SLC

Standby/Alarm .082 mA

mA

mA

SD505-DUCTR

(50 max.)

Aux. Pwr

Standby: 20 mA

2

mA

Alarm: 62 mA

2

mA

SLC

Standby/Alarm: .5 mA

mA

mA

SD505-DTS-K

(50 max.)

None, included with SD505-DUCTR worst case.

SD505-DUCT

(50 max.)

SLC

Standby/Alarm: .5 mA

mA

mA

SLC Isolator Devices

SD500-LIM

(100 max.)

Standby/Alarm .092 mA

mA

mA

SD505-6IB

(50 max.)

Accessories Modules

5860 Remote Fire Alarm
Annunciator

(8 max.)

Standby: 20 mA

mA

Alarm: 25 mA

mA

5824 Serial / Parallel Module

(2 max.)

Standby/Alarm: 45 mA

mA

mA

5496 Notification Power
Expander

(8 max.)

Standby/Alarm: 10 mA

mA

mA

5895XL Intelligent Power
Expander

Standby/Alarm 10 mA

mA

mA

5865-4 LED Annunciator

(with reset and silence switches)

(8 max.)

Standby: 35 mA

mA

Alarm: 145 mA

mA

5865-3 LED Annunciator

Standby: 35 mA

mA

Alarm: 145 mA

mA

5880 Generic LED Driver Module

Standby: 35 mA

mA

Alarm: 200 mA

mA

5883 Relay Interface

(32 max.)

Standby: 0 mA

mA

Alarm: 220 mA

(22 mA per relay)

mA

A

Total System Current

Auxiliary Devices

3

Refer to devices manual for current rating.

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Table 3-3: Current Calculation Worksheet for SD Devices

Device

# of

Devices

Current per Device

Standby

Current

Alarm

Current