Programming Overview
151295
6-2
output when a supervisory condition occurs.
Circuit 4 (Relay 2):
Assigned to Group 125. JumpStart automatically programs Zone 1 to activate Group 125 using constant on
output when an alarm occurs.
Addressable output points (Relay modules):
All addressable relay devices will be configured as “Output Pt” (general purpose output point) and assigned to
Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
6.1.3
Running JumpStart
Run JumpStart immediately after addressing and connecting all input devices (detectors, pull stations, and so on)
and output devices (notification appliances, relays, and so on).
Note: To install a few devices manually after running JumpStart, see Section 7.
To run JumpStart:
1.
Press
ENTER
to view the Main Menu.
2.
Select 7 for Program Menu.
3.
From the next menu, select 6 for JumpStart.
4.
When the message “WARNING Will DELETE all system options” displays, select Yes. A series of mes-
sages displays for the next several seconds. JumpStart scans the SLC loops for devices and can take several
minutes, depending on the number of devices attached.
5.
When message “SLC Family” flashes, Press ENTER to accept SK, or press
to change to SD and press
ENTER to accept
.
6.
When the message “Configuring System Done” displays, press any key to continue.
7.
Select one of the following options from the menu that displays.
1 - Review System
Press 1 if you need to review the JumpStart configuration.
2 - Repeat JumpStart
Press 2 if you need to rerun JumpStart for any reason.
3 - Accept Changes
1. If you are ready to make the JumpStart configuration permanent, select 3.
2. The system will ask you if the installation contains duct detectors. If there are none, select 2 for
No and skip to Step 8. If the system contains duct detectors, select 1 for Yes and continue with
Step 3.
3. From the list, select the SLC device that contains the duct detectors.
4. The first photoelectric detector on the system will display. Select 1 for DUCT and 2 for Non-
DUCT.
5. Press
to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue until all
duct detectors have been selected. (Note: You can move backwards through the list with
.)
6. When you reach the last detector on this device, press
.
7. The system will ask you if there are more duct detectors in the system. If there are, select 1 for
Yes and repeat from Step 3. If there are no more duct detectors, select 2 for No and continue with
Step 8.
8. The system will restart in 10 seconds, or press 1 to restart immediately.
9. After the system resets, it will use the new JumpStart configuration.
4 - Enter Programming
To go directly to Program Mode to configure any devices, press 4. The Programming Menu appears and you can
begin programming.