beautypg.com

See figure 7-13, nex, Figure 7-13 – SilentKnight 5700 User Manual

Page 120

background image

Programming

151295

7-22

each field.

Figure 7-13 Reporting Account Editing Screen

Select Account (ID)

The control panel provides up to 4 reporting accounts. The priority of an account is based on its account ID.
Account 1 is highest priority; Account 4 is lowest. Use Account 1 to report the highest priority events.

6.

Press the

or

arrow to select account ID number, then press

ENTER

.

Edit Account Number

Enter an up-to-6-digit number for each account to identify the account to the central station. See Figure 7-13 for
location of this option on the screen. The account number should be compatible with the reporting format used.
For example, the Contact ID format transmits up to four digits only.

7.

Enter the desired account number (up to 6-digits), then press

ENTER

.

Select Reporting Format

Select a reporting format for each account. Options are:

8.

Press the

or

arrow to select the reporting format, then press

ENTER

.

Events to Report

The next five options select which types of events (or event families) will be reported to this account. (See Figure
7-13 fo
r location of these options on the screen).

9.

Press the

or

arrow to select Must, Yes, or No (see Table below), then press

ENTER

.

SIA

SIA format. 8 events per call.

CID

Ademco’s Contact ID format

S20

Same as SIA reports up to 20 events per phone call.

Event Family

Events Included in this Family

Alarms

All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches, etc.)

Alarm Restore

All alarm restores.

Supervisory, Trouble, Enable/
Disable Point

All trouble and supervisory conditions and trouble and supervisory restores.
Enabling and disabling of input and output points.

Service/Test

Fire drill, walk test, dialer test, automatic test, all programming sessions.

System Reset

All system resets.