See figure 7-13, nex, Figure 7-13 – SilentKnight 5700 User Manual
Page 120

Programming
151295
7-22
each field.
Figure 7-13 Reporting Account Editing Screen
Select Account (ID)
The control panel provides up to 4 reporting accounts. The priority of an account is based on its account ID.
Account 1 is highest priority; Account 4 is lowest. Use Account 1 to report the highest priority events.
6.
Press the
or
arrow to select account ID number, then press
ENTER
.
Edit Account Number
Enter an up-to-6-digit number for each account to identify the account to the central station. See Figure 7-13 for
location of this option on the screen. The account number should be compatible with the reporting format used.
For example, the Contact ID format transmits up to four digits only.
7.
Enter the desired account number (up to 6-digits), then press
ENTER
.
Select Reporting Format
Select a reporting format for each account. Options are:
8.
Press the
or
arrow to select the reporting format, then press
ENTER
.
Events to Report
The next five options select which types of events (or event families) will be reported to this account. (See Figure
7-13 for location of these options on the screen).
9.
Press the
or
arrow to select Must, Yes, or No (see Table below), then press
ENTER
.
SIA
SIA format. 8 events per call.
CID
Ademco’s Contact ID format
S20
Same as SIA reports up to 20 events per phone call.
Event Family
Events Included in this Family
Alarms
All alarms (Water Flow, Manual Pull, Detectors, Auxiliary Switches, etc.)
Alarm Restore
All alarm restores.
Supervisory, Trouble, Enable/
Disable Point
All trouble and supervisory conditions and trouble and supervisory restores.
Enabling and disabling of input and output points.
Service/Test
Fire drill, walk test, dialer test, automatic test, all programming sessions.
System Reset
All system resets.