Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 99

Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
99
Frame 11 Mechanical Installation
Chapter 7
Table 25 - Power Terminal Specifications
Figure 36 - Power Terminal Locations
No. Name
Description
Wire Size Range
(1)(2)
Torque
Terminal Bolt Size
(3)(4)
Maximum
Minimum
Recommended
1
Input Power Terminal Block
(3)
1L1, 1L2, 1L3, 2L1, 2L2, 2L3
AC Input power
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M12
2
Output Power Terminal Block
(3)
U/T1, V/T2, W/T3
Motor connections
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M12
3
SHLD Terminal, PE, Motor Ground
(3)
Terminating point for wiring shields
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M10
4
DC Bus
(3)
(2 Terminals; DC–, DC+)
DC input or external brake
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N
•
m
(354 lb
•
in)
M12
5
Cable Clamp for Shield
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
(2) Do Not exceed maximum wire size. Parallel connections may be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal.
2L1
2L2
2L3
1L1
1L2
1L3
U/T1
V/T2
W/T3
DC-
DC+
Note: 600V AC input, 460A and 502A frame 11 drives only
have one set of Input Power Terminals.
4
2
1
5
3