Output power wiring – Rockwell Automation 20D PowerFlex 700H and 700S Frame 9...14 Drives User Manual
Page 116
116
Rockwell Automation Publication PFLEX-IN006E-EN-P - July 2013
Chapter 8
Frame 12 Mechanical Installation
Output Power Wiring
Frame 12 drives utilize two parallel power structures, and therefore have two sets
of output power terminals. You must connect the motor to both sets of output
power terminals.
Figure 46 - Frame 12 Motor Wiring Example
IMPORTANT
Parallel wiring must have the same cable dimensions, type and routing. Non-
symmetrical wiring may cause unequal loading between the converters and
reduce the drive’s ability to deliver current to the motor.
IMPORTANT
The minimum cable length for parallel motor cables from the drive to the point
where the cables connect is 5 m (16.4 ft). Join the parallel cables at the motor
end (not the drive end). Or, install a reactor on the output of each power
module with a minimum of 5 μH prior to joining the parallel cables at the
motor end.
IMPORTANT
Once power wiring has been completed, the protective covers must be
installed before energizing the drive. Installation is in reverse order of removal
(see Remove the Protective Covers on page
1T1
1T2
1T3
2T1
2T2
2T3
PE
PE
Motor Frame
Motor
5 m
minimum